| Plan Review Notes For Permit 11020032 |
| Permit Number |
11020032 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-02-23 09:04:30 | SHOW REQUIRED SAFETY CLEARANCES FOR THE ELECTRIC | | | SERVICE. NEC 110.26 | | | THE AUXILIARY GUTTER FOR THE SERVICE IS UNDER SIZED. | | | NEC 366.6, 366.56 | | | VERIFY THE ELECTRICAL EQUIPMENT HAS SUFFICIENT | | | INTERRUPTING RATING. NEC 110.9 | | | PROVIDE AUTOMATIC LIGHTING CONTROL. FBC 13-415 ABC.1.2 | | | PROVIDE LIGHTING DENSITY CALCULATION. FBC 13-415 ABC.1 | | | ON SHEET E-2.01 PROVIDE A PANEL SCHEDULE FOR MAIN # 1. | | | PROVIDE AN INTERSYSTEM BONDING BAR AT THE SERVICE. NEC | | | 250.94 | | | | | | ROBERT LECKY, ELECTRICAL PLAN REVIEW, 561-805-6718 | | | | | | |
|