2011-02-14 14:07:08RESIDENTIAL (R3) ADDITION, PLUMBING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
  
 PLUMBING RISER DIAGRAM:
 1- WET VENTING IS ONLY ALLOWED FOR BATHROOM FIXTURES.
 SEE SEC. P3108.1 OF THE 2007 FLORIDA RESIDENTIAL CODE
 AND REVISE AS REQUIRED.
  
 2- CLARIFY WHAT IS "COV" SHOWN ON THE 3" DRAIN.
  
 3- RISER DIAGRAM SHOWS 3" DRAIN TO CONNECT "TO EXISTING
 SEPTIC". SEPTIC TANKS ARE NOT ALLOWED IN THE CITY.
 REVISE AS REQUIRED.
  