| Plan Review Notes For Permit 11020011 |
| Permit Number |
11020011 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-02-17 13:42:25 | | | | THE SERVICE AS SHOWN WITH A 125 AMP MAIN BREAKER | | | REQUIRES A LARGER CONDUCTOR, GROUND AND CONDUIT. THE #6 | | | ELECTRICAL FEED TO THE 125 AMPERE GARAGE PANEL IS UNDER | | | SIZED. NEC 230.90, 310.16 | | | | | | ALL GENERAL PURPOSE RECEPTACLES WITHIN THE GARAGE | | | INCLUDING THE WORKSHOP AREA MUST BE GFCI PROTECTED. NEC | | | 210.8 | | | | | | ROBERT LECKY, ELECTRICAL PLAN REVIEW, 561-805-6718 |
|