| 2011-02-14 16:44:27 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) ROOF SHINGLES. |
| | |
| | B) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| | |
| | C) ACCORDING TO MIAMI-DADE WEBSITE GARAGE DOOR NOA |
| | 08-0718.01 WAS SUPERSEDED BY NOA 09-0604.03. PROVIDE |
| | CURRENT NOA 09-0604.03. |
| | |
| | D) PROVIDE NOA FOR JELD WEN SWING DOOR FOR SIZE OF DOOR |
| | SPECIFIED ON PLANS. NOA 07-0709.07 SUBMITTED IS FOR |
| | 8'-0" HIGH DOORS. |
| | |
| | 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 OF CITY AMENDMENTS TO FBC. |
| | |
| | 3- SPECIFY ATTIC ACCESS SIZE AND LOCATION ON PLANS AS |
| | REQUIRED BY SEC. R807 OF 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | 4- CLARIFY HOW IS THE GARAGE GOING TO BE ACCESSED. SITE |
| | PLAN DOESN'T SHOW ANY DRIVEWAY AND THE EXISTING |
| | CARPORT/STORAGE IS BLOCKING THE ACCESS. |
| | |
| | 5- SHEET #1: |
| | A) UPDATE GENERAL NOTE #1. REFER TO CURRENT CODE 2007 |
| | FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | B) REVISE GENERAL NOTE #26. ROOF ZONE #3 ALSO REQUIRES |
| | 8D RING SHANK NAILS @ 4"O.C.. SEE SEC. R803.2.3.1 OF |
| | 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | 6- SECTION "A" ON SHEET #3: |
| | A) REVISE VERTICAL REINFORCEMENT SPACING TO MATCH |
| | FOUNDATION PLAN. |
| | |
| | B) SPECIFY FINISH GRADE AS REQUIRED BY SEC. R404.1.6 OF |
| | 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | 7- TRUSS PACKAGE: |
| | A) TRUSS ENGINEER TO PROVIDE ORIGINAL SIGNATURE IN ALL |
| | SHEETS AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES. NO |
| | RUBBER STAMP. |
| | |
| | B) ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | TRUSS PACKAGE BEFORE SUBMITTAL TO THIS OFFICE. |
| | |
| | 8- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. SEC. 108.3 CITY AMENDMENTS TO FBC. VALUATION TO |
| | INCLUDE ALL LABOR, MATERIALS AND ENGINEERING SERVICES. |
| | VALUATION WAS UPDATED TO $30,000. PERMIT FEE BALANCE IS |
| | $632.70. |
| | |