| Plan Review Notes For Permit 11010709 |
| Permit Number |
11010709 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-02-10 08:30:40 | 777 SOUTH FLAGLER DRIVE, 6TH FLOOR COMMON AREA | | | PERMIT NUMBER 11010709 | | | | | | | | | 1. PLEASE INDICATE COMPLIANCE METHODS REGARDING THE | | | ELEVATOR LOBBY. PLEASE INDICATE ON THE PLANS HOW | | | COMPLIANCE IS ACHIEVED WITHOUT THE INSTALLATION OF | | | LOBBY DOORS. PLEASE INDICATE WHAT EXCEPTION CURRENTLY | | | EXISTS WHICH ALLOWS THE NON INSTALLATION OF THESE | | | DOORS. | | | | | | 2. ELEVATOR WARNING SIGNS REQUIRED IN ELEVATOR LOBBIES. | | | | | | 3. THE INSTALLATION OF NEW SOFFITS SHALL NOT INTERFERE | | | WITH THE OPERATION OF ANY FIRE SPRINKLER HEADS. | | | | | | 4. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM | | | AND FIRE SPRINKLER REMODELING. | | | | | | 5. TACTILE SIGNAGE REQUIRED AT EXIT DOORS. | | | | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|