Plan Review Notes
Plan Review Notes For Permit 11010708
Permit Number 11010708
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-02-04 13:26:501555 PALM BEACH LAKES BOULEVARD, SUITE #406
 PERMIT #11010708
 REVIEW COMMENTS - FIRE
  
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 IF THE DOOR IN BREAK ROOM 408 IS NOT INTENDED AS A
 MEANS OF EGRESS THE DOOR SHALL BE LABELED NO EXIT. THE
 WORD NO SHALL BE SPELLED IN LETTERS AT LEAST 2-INCHES
 HIGH. THE WORD EXIT SHALL BE SPELLED IN LETTERS AT
 LEAST 1-INCH HIGH.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND FIRE ALARM SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  