| Plan Review Notes For Permit 11010629 |
| Permit Number |
11010629 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-02-04 11:54:10 | DENIED BY PLUMBING | | | | | | 1) THE WASHING MACHINE ON THE SECOND FLOOR IS NOT SHOWN | | | ON THE PLUMBING ISOMETRIC DRAWING ON SHEET E-3. PLEASE | | | SHOW ON DRAWINGS. | | | | | | 2) THE TWO WATER CLOSETS IN HIS AND HER BATH ARE NOT | | | VENTED ON THE ISOMETRIC DRAWING. PLEASE CORRECT PER FBC | | | R P3101.2.1. | | | | | | 3) THE WET VENT FOR THE FIRST FLOOR GUEST BATHROOM IS | | | DOWNSTREAM OF THE TWO FIXTURES IT IS VENTING. PLEASE | | | CORRECT PER FBC R P3108.1. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|