| Plan Review Notes For Permit 11010629 |
| Permit Number |
11010629 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-02-04 16:16:05 | DENIED BY MECHANICAL | | | | | | 1) ON SHEET M-1 THE WALL AT LAUNDRY ROOM #1 ON THE | | | FIRST FLOOR IS SHOWN IN A DIFFERENT LOCATION THAN ON | | | A-1 OF THE ARCHITECTURAL PLAN. IF THE WALL IS LOCATED | | | AS SHOWN ON A-1 THE RETURN LOCATED IN THE LAUNDRY ROOM | | | WILL VIOLATE CODE SECTION M1602.2(3) OF THE 2007 FBC | | | RESIDENTIAL CODE. PLEASE CORRECT. | | | | | | 2) SHOW COMPLIANCE WITH FBCR M1305.1.3 FOR ACCESS TO | | | THE AIR HANDLER UNITS LOCATED IN THE ATTIC. | | | | | | 3) ON SHEET M-1 THE TRANSFER DUCT FROM THE GUEST | | | BEDROOM IS TOO SMALL. FBCR M1602.4 REQUIRES THE | | | TRANSFER DUCT TO BE 1.5 TIMES THE CROSS SECTIONAL AREA | | | OF THE SUPPLY DUCTS ENTERING THE SPACE IT'S SERVING. | | | PLEASE CORRECT. | | | | | | 4) THE FLOOR PLAN FOR THE MASTER BATH ON SHEET M-2 DOES | | | NOT CORRESPOND WITH THE ONE ON A-2. PLEASE CORRECT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|