2011-02-03 15:07:50PROVIDE AN INTERSYSTEM BONDING STRIP AT THE SERVICE.
 NEC 250.94
 PROVIDE THE INTERRUPTING (AIC) CURRENT RATING FOR THE
 ELECTRICAL SERVICE. NEC 110.9
 NOTE ON THE PLAN THAT THE SMOKE DETECTORS ARE TO BE
 INTERCONNECTED. FBC R313.2
 PROVIDE AN APPLIANCE RECEPTACLE OUTLET AT THE ISLAND
 COUNTERTOP SPACE. NEC 210.50(C)(2).
 PROVIDE A SUPPORTING CALCULATION FOR THE REDUCTION IN
 SIZE OF THE GROUNDED CONDUCTOR (NEUTRAL) NEC 310.15 (A)
 (6), 215.2
 PROVIDE A LIGHTING OUTLET AND A SWITCH FOR THE ATTIC
 STORAGE AREA. NEC 210.70(3)
 NOTE ON THE PLANS THE REQUIRED WORKING CLEARANCES FOR
 THE AC COMPRESSOR DISCONNECTS. NEC 110.26
 NOTE THE SERVICE EQUIPMENT AND WIRE WAY MUST BE LISTED
 FOR OUTDOOR USE. NEC 110.11
 LOCATE THE ELECTRIC SERVICE EQUIPMENT AND ELECTRIC
 PANELS ON THE PLAN. COORDINATE THE LOCATION OF THE AC
 UNITS, SEE SHEET E-1 AND M- 1.