| Notes |
| Date |
Text |
| 2011-02-03 15:07:50 | PROVIDE AN INTERSYSTEM BONDING STRIP AT THE SERVICE. | | | NEC 250.94 | | | PROVIDE THE INTERRUPTING (AIC) CURRENT RATING FOR THE | | | ELECTRICAL SERVICE. NEC 110.9 | | | NOTE ON THE PLAN THAT THE SMOKE DETECTORS ARE TO BE | | | INTERCONNECTED. FBC R313.2 | | | PROVIDE AN APPLIANCE RECEPTACLE OUTLET AT THE ISLAND | | | COUNTERTOP SPACE. NEC 210.50(C)(2). | | | PROVIDE A SUPPORTING CALCULATION FOR THE REDUCTION IN | | | SIZE OF THE GROUNDED CONDUCTOR (NEUTRAL) NEC 310.15 (A) | | | (6), 215.2 | | | PROVIDE A LIGHTING OUTLET AND A SWITCH FOR THE ATTIC | | | STORAGE AREA. NEC 210.70(3) | | | NOTE ON THE PLANS THE REQUIRED WORKING CLEARANCES FOR | | | THE AC COMPRESSOR DISCONNECTS. NEC 110.26 | | | NOTE THE SERVICE EQUIPMENT AND WIRE WAY MUST BE LISTED | | | FOR OUTDOOR USE. NEC 110.11 | | | LOCATE THE ELECTRIC SERVICE EQUIPMENT AND ELECTRIC | | | PANELS ON THE PLAN. COORDINATE THE LOCATION OF THE AC | | | UNITS, SEE SHEET E-1 AND M- 1. | | | ATTIC | | | | | | ROBERT LECKY, ELECTRIC PLAN REVIEW, 561-805-6718 | | | |
|