| 2011-02-16 12:40:55 | PROJECT: 1400 VILLAGE BLVD./CASCADE APARTMENTS/BUILDING |
| | #3 |
| | |
| | CODE REVIEW: |
| | |
| | 2007 FLORIDA EXISTING BUILDING CODE W/2009 SUPPLEMENTS |
| | 2004 FLORIDA BUILDING CODE W/ 2009 SUPPLEMENTS |
| | CITY OF WEST PALM BEACH AMENDMENTS 2004 EDITION |
| | |
| | PLAN REVIEW NOTES: |
| | |
| | 1) FEBC, SECTION 506.2.4- LESS THAN SUBSTANTIAL |
| | STRUCTURAL DAMAGE. FOR DAMAGE LESS THAN SUBSTANTIAL |
| | STRUCTURAL DAMAGE, REPAIRS SHALL BE ALLOWED THAT |
| | RESTORE THE BUILDING TO ITS PREDAMAGED STATE USING |
| | MATERIALS AND STRENGTHS THAT EXISTED PRIOR TO THE |
| | DAMAGE. NEW STRUCTURAL MEMBERS AND CONNECTIONS USED FOR |
| | THIS REPAIR SHALL COMPLY WITH THE DETAILING PROVISIONS |
| | OF THE FLORIDA BUILDING CODE, BUILDING FOR NEW |
| | BUILDINGS OF SIMILAR STRUCTURE, PURPOSE AND LOCATION. |
| | |
| | 2) 504.1 GENERAL. REPAIRS SHALL BE DONE IN A MANNER |
| | THAT MAINTAINS THE LEVEL OF PROTECTION PROVIDED FOR THE |
| | MEANS OF EGRESS. |
| | |
| | 3) 2308.8.2 FRAMING DETAILS. JOISTS SHALL BE SUPPORTED |
| | LATERALLY AT THE ENDS AND AT EACH SUPPORT BY SOLID |
| | BLOCKING EXCEPT WHERE THE ENDS OF THE JOISTS ARE NAILED |
| | TO A HEADER, BAND OR RIM JOIST OR TO AN ADJOINING STUD |
| | OR BY OTHER MEANS. SOLID BLOCKING SHALL NOT BE LESS |
| | THAN 2 INCHES (51MM) IN THICKNESS AND THE FULL DEPTH OF |
| | THE JOIST. NOTCHES ON THE ENDS OF JOISTS SHALL NOT |
| | EXCEED ONE-FOURTH THE JOIST DEPTH. HOLES BORED IN |
| | JOISTS SHALL NOT BE WITHIN 2 INCHES (51 MM) OF THE TOP |
| | OR BOTTOM OF THE JOIST, AND THE DIAMETER OF ANY SUCH |
| | HOLE SHALL NOT EXCEED ONE-THIRD THE DEPTH OF THE JOIST. |
| | NOTCHES IN THE TOP OR BOTTOM OF JOISTS SHALL NOT EXCEED |
| | ONE-SIXTH THE DEPTH AND SHALL NOT BE LOCATED IN THE |
| | MIDDLE THIRD OF THE SPAN. |
| | |
| | SEE DETAIL 3-D.1. NOTCHING AT ENDS SHALL NOT EXCEED 25% |
| | OF THE INDICATED DEPTH. |
| | |
| | ***PROVISO**** |
| | |
| | 1) PROVIDE CALCULATED LOADS AT FLOOR SECTIONS WHERE 2" |
| | CONCRETE IS TO BE PLACED. |
| | 2) PROVIDE DETAILS OF DRAINAGE AT REPAIRED BALCONIES. |
| | 3) DETAILED SECTIONS NOT INDICATED ON PLAN LAYOUT. |
| | MISSING SHEETS? PLEASE CORRECT. |
| | 4) PLEASE INDICATE THE GRADE AND SPECIES OF THE LUMBER |
| | TO BE USED FOR THE REPAIR: FBC, SECTION |
| | 2303.1.1/2303.1.8. |
| | 5) PROVIDE PRODUCT APPROVALS FOR THE SPECIFIED |
| | STRAPS/ANCHORS. |
| | |
| | PLAN REVIEWER: |
| | |
| | KEN CONRAD |
| | 561-805-6666 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |