| 2011-02-04 15:08:20 | 1009 BANYAN BOULEVARD | | | WATER TREATMENT PLANT | | | PERMIT #11010553 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | | | | THE PROJECT ADDRESS ON THE PERMIT APPLICATION IS IN | | | CONFLICT WITH THE TITLE BLOCK ADDRESS SHOWN ON THE | | | PLANS. | | | | | | FIRE DEPARTMENT ACCESS ROADS SHALL HAVE A SURFACE | | | DESIGNED TO ACCOMMODATE FIRE APPARATUS WEIGHING AT | | | LEAST 32 TONS. ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED | | | WIDTH OF NOT LESS THAN 20 FEET AND AN UNOBSTRUCTED | | | VERTICAL CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES | | | PER SECTION 18.2.3.4.1.1 OF NFPA 1 OF THE FLORIDA FIRE | | | PREVENTION CODE. | | | | | | KNOX GATE ACCESS KEY SWITCH CAN BE ORDERED FROM | | | WWW.KNOXBOX.COM. | | | | | | PLEASE EXPLAIN IF ANY NEW FIRE SERVICE MAINS OR FIRE | | | HYDRANTS TO BE INSTALLED. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|