Plan Review Notes
Plan Review Notes For Permit 11010553
Permit Number 11010553
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-02-04 15:08:201009 BANYAN BOULEVARD
 WATER TREATMENT PLANT
 PERMIT #11010553
 REVIEW COMMENTS - FIRE DEPARTMENT
  
  
 THE PROJECT ADDRESS ON THE PERMIT APPLICATION IS IN
 CONFLICT WITH THE TITLE BLOCK ADDRESS SHOWN ON THE
 PLANS.
  
 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE A SURFACE
 DESIGNED TO ACCOMMODATE FIRE APPARATUS WEIGHING AT
 LEAST 32 TONS. ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED
 WIDTH OF NOT LESS THAN 20 FEET AND AN UNOBSTRUCTED
 VERTICAL CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES
 PER SECTION 18.2.3.4.1.1 OF NFPA 1 OF THE FLORIDA FIRE
 PREVENTION CODE.
  
 KNOX GATE ACCESS KEY SWITCH CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PLEASE EXPLAIN IF ANY NEW FIRE SERVICE MAINS OR FIRE
 HYDRANTS TO BE INSTALLED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  