| Plan Review Notes For Permit 11010553 |
| Permit Number |
11010553 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-02-10 09:12:47 | VERIFY THE EXISTING 480 VOLT SERVICE (SHEET E10) HAS A | | | SERVICE RATED MAIN DISCONNECT. | | | IT IS UNCLEAR ON THE PLANS (SHEET E10) THAT AN | | | EFFECTIVE GROUND-FAULT CURRENT PATH IS AVAILABLE FOR | | | THE STREET LIGHT SYSTEM. | | | PROVIDE AN ENGINEERED LIGHT POLE FOOTING DESIGNED FOR | | | THE WIND LOAD SPECIFIED. (SHEET E 8) | | | PROVIDE CERTIFICATION FROM THE ENGINEER OF RECORD ON | | | THE POLE DESIGN FOR THE WIND LOAD SPECIFIED. (SHEET E | | | 8) | | | | | | ROBERT LECKY, ELECTRICAL PLAN REVIEW, 561-805-6718 | | | | | 2011-02-09 16:15:05 | | | | |
|