| Plan Review Notes For Permit 11010541 |
| Permit Number |
11010541 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-02-17 13:35:42 | 1009 BANYAN BOULEVARD | | | PERMIT NUMBER 11010541 | | | REPLACEMENT OF EXISTING FLUORIDE SYSTEM WITH A NEW | | | FLUORIDE STORAGE AND FEED SYSTEM. | | | | | | | | | 1. SITE ADDRESS NOT LISTED ON THE PLANS. | | | | | | 2. ALL STORAGE VESSELS ARE TO BE PROPERLY IDENTIFIED | | | WITH PRODUCT NAME AND QUANTITY. | | | | | | 3. ALL CONSTRUCTION, DEMOLITION, AND RENOVATION TO | | | COMPLY WITH NFPA 241. | | | | | | 4. ALL HAZARDOUS MATERIALS ARE TO BE PROPERLY STORED, | | | HANDLED, AND TRANSFERRED DURING THE PROPOSED | | | RENOVATIONS. | | | | | | 5. ACCORDING TO THE MATERIAL SAFETY DATA SHEETS (MSDS) | | | THAT WERE PROVIDED THE HYDROFLUOROSILICIC ACID | | | SIGNIFICANT HEALTH HAZARDS EXIST SHOULD EYE, SKIN, | | | INHALATION OR INGESTION OCCURS. THIS MATERIAL HAS A | | | HEALTH HAZARD OF A 3 ON THE NFPA 704 IDENTIFICATION | | | PLACARD. ALSO THE SULFURIC ACID IS ALSO LISTED AS A 3 | | | ON THE NFPA 704 IDENTIFICATION PLACARD. | | | | | | 6. MORE DETAILS NEEDED FOR CONDUIT PENETRATION AT NEW | | | WALL OR SLAB DETAIL SHOWN ON SHEET E-9. THE TYPE OF | | | FIRE RATING MATERIAL, THICKNESS OF APPLICATION, AND | | | INSTALLATION METHODS SHOULD BE PROVIDED. | | | | | | 7. WRONG CODE INFORMATION PROVIDED ON SHEET E-2. SHOULD | | | READ THE 2006 EDITION OF THE LIFE SAFETY CODE, NFPA 101 | | | NOT THE 2003 EDITION. | | | | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|