Plan Review Notes
Plan Review Notes For Permit 11010541
Permit Number 11010541
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-02-17 13:35:421009 BANYAN BOULEVARD
 PERMIT NUMBER 11010541
 REPLACEMENT OF EXISTING FLUORIDE SYSTEM WITH A NEW
 FLUORIDE STORAGE AND FEED SYSTEM.
  
  
 1. SITE ADDRESS NOT LISTED ON THE PLANS.
  
 2. ALL STORAGE VESSELS ARE TO BE PROPERLY IDENTIFIED
 WITH PRODUCT NAME AND QUANTITY.
  
 3. ALL CONSTRUCTION, DEMOLITION, AND RENOVATION TO
 COMPLY WITH NFPA 241.
  
 4. ALL HAZARDOUS MATERIALS ARE TO BE PROPERLY STORED,
 HANDLED, AND TRANSFERRED DURING THE PROPOSED
 RENOVATIONS.
  
 5. ACCORDING TO THE MATERIAL SAFETY DATA SHEETS (MSDS)
 THAT WERE PROVIDED THE HYDROFLUOROSILICIC ACID
 SIGNIFICANT HEALTH HAZARDS EXIST SHOULD EYE, SKIN,
 INHALATION OR INGESTION OCCURS. THIS MATERIAL HAS A
 HEALTH HAZARD OF A 3 ON THE NFPA 704 IDENTIFICATION
 PLACARD. ALSO THE SULFURIC ACID IS ALSO LISTED AS A 3
 ON THE NFPA 704 IDENTIFICATION PLACARD.
  
 6. MORE DETAILS NEEDED FOR CONDUIT PENETRATION AT NEW
 WALL OR SLAB DETAIL SHOWN ON SHEET E-9. THE TYPE OF
 FIRE RATING MATERIAL, THICKNESS OF APPLICATION, AND
 INSTALLATION METHODS SHOULD BE PROVIDED.
  
 7. WRONG CODE INFORMATION PROVIDED ON SHEET E-2. SHOULD
 READ THE 2006 EDITION OF THE LIFE SAFETY CODE, NFPA 101
 NOT THE 2003 EDITION.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION