| Plan Review Notes For Permit 11010475 |
| Permit Number |
11010475 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-01-27 15:05:12 | 1555 PALM BEACH LAKES BOULEVARD, SUITE 200 & 205 | | | PERMIT #11010475 | | | REVIEW COMMENTS - FIRE | | | | | | | | | PROVIDE A PORTABLE FIRE EXTINGUISHER FOR SUITE 205. | | | | | | EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE | | | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING | | | FIRE/SMOKE BARRIER PROTECT ALL OPENINGS. CHARACTERS | | | SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN | | | WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 | | | FEET ON CENTER. (REFERENCE: SECTION 8.3.2.4 OF FLORIDA | | | FIRE PREVENTION CODE ??? NFPA 101) | | | | | | PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL | | | BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. | | | (REFERENCE: SECTION 8.3.5.1 OF FLORIDA FIRE PREVENTION | | | CODE ??? NFPA 101) | | | | | | SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE SPRINKLER | | | AND FIRE ALARM WORK. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | | | | |
|