Date Text
2011-01-27 15:05:121555 PALM BEACH LAKES BOULEVARD, SUITE 200 & 205
 PERMIT #11010475
 REVIEW COMMENTS - FIRE
  
  
 PROVIDE A PORTABLE FIRE EXTINGUISHER FOR SUITE 205.
  
 EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER. (REFERENCE: SECTION 8.3.2.4 OF FLORIDA
 FIRE PREVENTION CODE ??? NFPA 101)
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE.
 (REFERENCE: SECTION 8.3.5.1 OF FLORIDA FIRE PREVENTION
 CODE ??? NFPA 101)
  
 SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE SPRINKLER
 AND FIRE ALARM WORK.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  
  