| Plan Review Notes For Permit 11010405 |
| Permit Number |
11010405 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-02-10 10:31:48 | PLAN RESUBMITALL IS INCOMPLETE AND INADEQUATELY | | | DETAILED. PLEASE ADD ADDITIONAL INFORMATION OR SCHEDULE | | | A MEETING TO DISCUSS. | | | | | | 3/0 WIRE IS REQUIRED TO FEED THE 200 AMP PANEL. | | | WHAT SIZE WIRE IS FEEDING THE 400 AMP PANEL? | | | WHAT SIZE WIRE IS FEEDING THE GUTTER. THE PLANS SHOW | | | TWO DIFFERENT SIZES. | | | SHOW THE GROUNDING WIRE SIZE FOR ALL CONDUITS. | | | WHAT IS THE INSULATION RATING FOR THE WIRE? | | | WHAT TYPE OF CONDUIT IS PROPOSED? | | | WHAT IS THE VOLTAGE OF THE SERVICE? | | | PROVIDE A SERVICE GROUNDING DETAIL. | | | | | | | | | | | | ROBERT LECKY, ELECTRIC PLANS EXAMINER, 561-805-6718 | | | |
|