2011-01-20 11:58:17PLANS ARE INCOMPLETE AND INADEQUATELY DETAILED. PLEASE
 REDRAW WITH ADDITIONAL INFORMATION OR SCHEDULE A
 MEETING TO DISCUSS.
  
 2/0 WIRE IS RATED FOR 175 AMPS. NEC 301.16.
 THE ???NEW??? PANEL APPEARS TO BE FED FROM A METER?
 WHICH PANEL BOARDS ARE FOR THE I-HOP?
 ARE THE MAIN SERVICE DISCONNECTS GROUPED?
 IS THERE ADEQUATE CLEARANCE FOR THE NEW EQUIPMENT?
 HOW IS THE NEW SERVICE AND DISCONNECT BEING FED?
 IS THIS PLAN AN " AS BUILT" OR A NEW INSTALLATION?
 PROVIDE A LOAD CALCULATION TO SUPPORT THE PROPOSED
 SERVICE SIZE.
 WHAT IS THE INSULATION RATING FOR THE WIRE?
 WHAT TYPE OF CONDUIT IS PROPOSED?
 WHAT IS THE VOLTAGE?
 WHAT IS THE FAULT CURRENT RATING REQUIRED FOR THE
 SERVICE?
  