| Plan Review Notes For Permit 11010405 |
| Permit Number |
11010405 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-01-20 11:58:17 | PLANS ARE INCOMPLETE AND INADEQUATELY DETAILED. PLEASE | | | REDRAW WITH ADDITIONAL INFORMATION OR SCHEDULE A | | | MEETING TO DISCUSS. | | | | | | 2/0 WIRE IS RATED FOR 175 AMPS. NEC 301.16. | | | THE ???NEW??? PANEL APPEARS TO BE FED FROM A METER? | | | WHICH PANEL BOARDS ARE FOR THE I-HOP? | | | ARE THE MAIN SERVICE DISCONNECTS GROUPED? | | | IS THERE ADEQUATE CLEARANCE FOR THE NEW EQUIPMENT? | | | HOW IS THE NEW SERVICE AND DISCONNECT BEING FED? | | | IS THIS PLAN AN " AS BUILT" OR A NEW INSTALLATION? | | | PROVIDE A LOAD CALCULATION TO SUPPORT THE PROPOSED | | | SERVICE SIZE. | | | WHAT IS THE INSULATION RATING FOR THE WIRE? | | | WHAT TYPE OF CONDUIT IS PROPOSED? | | | WHAT IS THE VOLTAGE? | | | WHAT IS THE FAULT CURRENT RATING REQUIRED FOR THE | | | SERVICE? | | | | | | ROBERT LECKY, ELECTRIC PLANS EXAMINER, 561-805-6718 | | | |
|