Notes
Date Text
2011-01-20 10:03:09REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. APPLICATION SCOPE OF WORK IS FOR CONDENSING UNIT
 REPLACEMENT. PLEASE SEE FBC 13-101.6, EXCEPTIONS (1):
  
 MATCHED SYSTEMS ARE REQUIRED; THIS MATCH MAY BE
 VERIFIED BY ANY ONE OF THE FOLLOWING MEANS:
  
 1. ARI (AHRI) DATA
 2. ACCREDITED LABORATORY (EXAMPLE ARL LABS)
 3. MANUFACTURER'S LETTER
 4. LETTER FROM REGISTERED P.E. STATE OF FLORIDA
  
 AS DISCUSSED, PLEASE PROVIDE DOCUMENTATION TO SHOW
 COMPLIANCE WITH FBC 13-101.6.
  