| Notes |
| Date |
Text |
| 2011-03-18 14:32:38 | PASS PROVISO | | | 1) PROVIDE A DETAIL FROM THE ENGINEER ON HOW THE | | | CONDENSOR STAND IS TIED TO THE ROOF. | | | AT FIRST INSPECTION . | | | 2) PROVIDE PRODUCT APPROVAL FOR CONDENSOR STAND AT | | | FIRST INSPECTION. | | | 3) PROVIDE A DETAIL ON THE PENETRATIONS THROUGH RATED | | | WALLS AND SHAFT. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|