Plan Review Notes
Plan Review Notes For Permit 11010398
Permit Number 11010398
Review Stop M
Sequence Number 2
Notes
Date Text
2011-02-17 10:53:36REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS FOR THE PURPOSE OF CONTINUITY.
  
 1. OK
  
 2. OK
  
 3. OK
  
 4. PAGE M-1 NOW SHOWS 10" ROUND DUCT TO "EXISTING WALL
 CAP." THE LOCATION OF THIS WALL CAP IS NOT SHOWN ON
 PLANS, BUT IT APPEARS TO BE AT THE BACK OF THE SPACE.
 THERE IS AN EXISTING ALLEY AT THIS LOCATION. OUTDOOR
 AIR INTAKE OPENINGS SHALL BE LOCATED A MINIMUM OF 10
 FEET HORIZONTALLY FROM LOT LINES, STREETS AND ALLEYS
 PER FBC-M 401.4 AND 401.4.1.
  
 5. WHAT TYPE OF DRAIN LINE WILL THE CONDENSATE PUMP BE
 CONNECTED TO FOR DISCHARGE? CITY ORDINANCE PROHIBITS
 DISCHARGE OF CONDENSATE INTO THE SANITARY DRAIN SYSTEM.
  
 6. NOT ADDRESSED
  
 NOTE: TEST AND BALANCE REPORT REQUIRED FOR FINAL
 INSPECTION PER FBC-M 403.3.4.
  
 NOTE: PLAN SHOWS WHAT APPEARS TO BE EXPOSED DUCT BOARD
 THROUGHOUT THE SPACE. PLEASE NOTE THAT EXPOSED
 DUCTBOARD CAN NOT BE PAINTED AS IT VOIDS THE FLAME
 SPREAD/SMOKE DEVELOPMENT RATING ASSOCIATED WITH THE
 UL181 LISTING OF THE DUCT.
  