| Plan Review Notes For Permit 11010398 |
| Permit Number |
11010398 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-02-17 10:53:36 | REVIEW #: 2ND | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | | PREVIOUS REVIEW COMMENTS FOR THE PURPOSE OF CONTINUITY. | | | | | | 1. OK | | | | | | 2. OK | | | | | | 3. OK | | | | | | 4. PAGE M-1 NOW SHOWS 10" ROUND DUCT TO "EXISTING WALL | | | CAP." THE LOCATION OF THIS WALL CAP IS NOT SHOWN ON | | | PLANS, BUT IT APPEARS TO BE AT THE BACK OF THE SPACE. | | | THERE IS AN EXISTING ALLEY AT THIS LOCATION. OUTDOOR | | | AIR INTAKE OPENINGS SHALL BE LOCATED A MINIMUM OF 10 | | | FEET HORIZONTALLY FROM LOT LINES, STREETS AND ALLEYS | | | PER FBC-M 401.4 AND 401.4.1. | | | | | | 5. WHAT TYPE OF DRAIN LINE WILL THE CONDENSATE PUMP BE | | | CONNECTED TO FOR DISCHARGE? CITY ORDINANCE PROHIBITS | | | DISCHARGE OF CONDENSATE INTO THE SANITARY DRAIN SYSTEM. | | | | | | 6. NOT ADDRESSED | | | | | | NOTE: TEST AND BALANCE REPORT REQUIRED FOR FINAL | | | INSPECTION PER FBC-M 403.3.4. | | | | | | NOTE: PLAN SHOWS WHAT APPEARS TO BE EXPOSED DUCT BOARD | | | THROUGHOUT THE SPACE. PLEASE NOTE THAT EXPOSED | | | DUCTBOARD CAN NOT BE PAINTED AS IT VOIDS THE FLAME | | | SPREAD/SMOKE DEVELOPMENT RATING ASSOCIATED WITH THE | | | UL181 LISTING OF THE DUCT. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|