2011-02-17 10:23:19THE PLAN RE-SUBMITTAL WAS INCOMPLETE.
  
 1. PROVIDE LIGHTING DENSITY CALCULATIONS SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING CODE REQUIREMENTS.
 FBC 13-415 ABC.1.2
 2. SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES.
 FBC 13-415 ABC.1.2.
 3. IT IS NOT ENOUGH TO SPECIFY ONLY THE AVAILABLE FAULT
 CURRENT AVAILABLE. YOU MUST ALSO DEMONSTRATE BY
 CALCULATION AND EQUIPMENT SELECTION HOW THE ELECTRICAL
 SYSTEM HAS BEEN DESIGNED TO HANDLE THE 61,315
 SYMMETRICAL AMPERES OF FAULT CURRENT. NEC 110.9, 110.10
 4. THE PROPOSED ELECTRICAL SERVICE RISER PLAN IS
 INCOMPLETE. PLEASE SHOW THE NEW SERVICE ON THE
 ELECTRICAL SHEETS; INDICATE WHERE THE AC PANEL IS
 LOCATED; SPECIFY THE WEATHER RESISTANCE CATEGORY FOR
 THE SERVICE ENCLOSURES. NOTE THHN WIRE IS SUITABLE FOR
 DRY LOCATIONS ONLY. NEC 110.3, 110.11, 110.20, 110.22,
 TABLE 310.13(A).
  
 ROBERT LECKY, ELECTRICAL PLAN REVIEW, 561-805-6718
  
  