| Plan Review Notes For Permit 11010398 |
| Permit Number |
11010398 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-02-17 10:23:19 | THE PLAN RE-SUBMITTAL WAS INCOMPLETE. | | | | | | 1. PROVIDE LIGHTING DENSITY CALCULATIONS SHOWING | | | COMPLIANCE WITH THE FLORIDA BUILDING CODE REQUIREMENTS. | | | FBC 13-415 ABC.1.2 | | | 2. SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE | | | CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES. | | | FBC 13-415 ABC.1.2. | | | 3. IT IS NOT ENOUGH TO SPECIFY ONLY THE AVAILABLE FAULT | | | CURRENT AVAILABLE. YOU MUST ALSO DEMONSTRATE BY | | | CALCULATION AND EQUIPMENT SELECTION HOW THE ELECTRICAL | | | SYSTEM HAS BEEN DESIGNED TO HANDLE THE 61,315 | | | SYMMETRICAL AMPERES OF FAULT CURRENT. NEC 110.9, 110.10 | | | 4. THE PROPOSED ELECTRICAL SERVICE RISER PLAN IS | | | INCOMPLETE. PLEASE SHOW THE NEW SERVICE ON THE | | | ELECTRICAL SHEETS; INDICATE WHERE THE AC PANEL IS | | | LOCATED; SPECIFY THE WEATHER RESISTANCE CATEGORY FOR | | | THE SERVICE ENCLOSURES. NOTE THHN WIRE IS SUITABLE FOR | | | DRY LOCATIONS ONLY. NEC 110.3, 110.11, 110.20, 110.22, | | | TABLE 310.13(A). | | | | | | ROBERT LECKY, ELECTRICAL PLAN REVIEW, 561-805-6718 | | | | | | |
|