2011-02-16 12:18:41BUILDING PLAN REVIEW
 PERMIT: 11010398
 ADD: 306 CLEMATIS ST/ 1ST FLOOR
 CONT: SCOT CORP INC.
 TEL: (561)346-9888
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 FEB. 16/ 2011
  
 ACTION: DENIED
  
 1A) COMPLIED.
  
 1B) NEW COMMENT: COVER SHEET PROJECT SCOPE PLEASE
 CORRECT OCCUPANT LOAD CALCS. IST FLOOR MERCANTILE
 3658/30= 122 OCCUPANT LOAD, SECOND FLOOR 3626/ 300=13
 OCCUPANTS.
  
 2) COMPLIED.
 (2A) COMPLIED.
  
 2B) THE NEW EXIT STAIRWAY LOCATED AT THE REAR OF THE
 BUILDING MUST COMPLY WITH EXISTING BUILDING CODE 701.3.
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2007 FBC-B 1020.1 ENCLOSURES REQUIRED. INTERIOR EXIT
 STAIRWAYS AND INTERIOR EXIT RAMPS SHALL BE ENCLOSED
 WITH FIRE BARRIERS CONSTRUCTED IN ACCORDANCE WITH
 SECTION 706 OR HORIZONTAL ASSEMBLIES CONSTRUCTED IN
 ACCORDANCE WITH SECTION 711, OR BOTH. EXIT ENCLOSURES
 SHALL HAVE A FIRE-RESISTANCE RATING OF NOT LESS THAN 2
 HOURS WHERE CONNECTING FOUR STORIES OR MORE AND NOT
 LESS THAN 1 HOUR WHERE CONNECTING LESS THAN FOUR
 STORIES.
  
 1020.1.2 PENETRATIONS. PENETRATIONS INTO AND OPENINGS
 THROUGH AN EXIT ENCLOSURE ARE PROHIBITED EXCEPT FOR
 REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK NECESSARY
 FOR INDEPENDENT PRESSURIZATION, SPRINKLER PIPING,
 STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT
 COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY SERVING
 THE EXIT ENCLOSURE AND TERMINATING AT A STEEL BOX NOT
 EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH
 PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 712. THERE SHALL BE NO PENETRATIONS OR
 COMMUNICATION OPENINGS, WHETHER PROTECTED OR NOT,
 BETWEEN ADJACENT EXIT ENCLOSURES.
  
 THE CODE LIMITS THE USE OF THIS AREA, RESTROOMS AND
 MECHANICAL ROOMS ARE NOT TO BE LOCATED WITHIN THE
 STAIRWELL. IF VIEWED AS AN EXIT PASSAGEWAY A DOOR WOULD
 STILL BE REQUIRED TO SEPERATE THE VERTICAL EXIT FROM
 THE EXIT PASSAGE WAY TO THE EXIT DISCHARGE. WITHIN THE
 EXIT PASSAGE WAY THE RESTROOM DOOR AND MECHANICAL ROOM
 DOOR WOULD STILL NEED TO BE RELOCTED OUT SIDE OF THE
 EXIT PASSAGE WAY.
  
 2C) CREATING A CIRCULAR STAIR AND A NEW UNPROTECTED
 FLOOR OPENING: THERE ARE TWO ISSUES,
 2C)(1) THE CIRCULAR STAIR NEEDS TO BE LOCATED WITHIN A
 VERTICAL EXIT ENCLOSURE,2007 FBC-B 1020.1.
 2C)(2) SHEET A-1INDICATES THE USE OF A 26" CIRCULAR
 STAIR PLEASE REVIEW 2007 FBC-B 1009.8.2 MEZZANINES AND
 1009.8.3 SPIRAL STAIRS IN
 DWELLING, DWELLING UNITS, GUEST ROOMS AND GUEST SUITES.
 THESE TWO CODE SECTIONS LIMIT THE USE OF A 26" SPIRAL
 STAIR AS A PART OF A
 MEANS OF EGRESS.
  
 2007 FBC-B 1009.8.1(1-6) PROVIDES THE CONDITIONS WHERE
 A SPIRAL STAIR CAN BE USED AS A PART OF A MEANS OF
 EGRESS. PLEASE REVIEW ALL THE CODE CRITERIA REQUIRED
 FOR A SPIRAL STAIR!!!!!!!! PLEASE PROVIDE SHOP DRAWINGS
 TO PROVIDE CODE COMPLIANCE WITH ALL SECTIONS OF
 1009.8.1 (1-6).
  
 3) COMPLIED.
  
 4-5)
  
 6)PROVISO: THIS WILL BE NOTED AS AN PROVISO ON PLANS,
 THE THIRD AND FOURTH FLOORS WILL NEED TO REMAIN
 UNOCCUPIED. SHEET A-1 ALSO INDICATES THE BLOCKING UP OF
 THE EXISTING ELEVATOR, THIS MAY CREATE CODE VIOLATIONS
 FOR THE 2ND FLOOR & 3RD FLOOR FOR VERTICAL
 ACCESSIBILITY. 11-4.1.6(III),& 11-4.1.6(1)(D)..
  
 7-8) COMPLIED.
  
 9) PROVISO: THE PLANS AS CURRENTLY DESIGNED DOES NOT
 TAKE EGRESS IN MIND FOR THE 3RD AND 4TH FLOORS, WILL
 NEED TO REMAIN UNOCCUPIED.
 2007 FBC-B 1014.2. THE MEANS OF EGRESS CAN NOT GO
 THROUGH A SEPERATE TENANCY .
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved