| Notes |
| Date |
Text |
| 2011-01-27 11:11:25 | FBC PLUMBING 2007 PLAN REVIEW #1 | | | DENIED: | | | | | | 1. IF STALLS ARE PROVIDED IN THE TOILET ROOMS, THEN | | | THEY SHALL COMPLY WITH 11-4.17 FIGURE(E) | | | | | | 2. FBC PLUNBING 403.1 MINIMUM NUMBER OF FIXTURES. 1 | | | DRINKING FOUNTAIN PER 1,000 OCCUPANTS IS REQUIRED. | | | | | | 3. FBC 106.3.5.1.3 WATER PIPING DIAGRAM IS REQUIRED. | | | | | | 3. PLEASE INDICATE ON PLAN WHERE THE FLOOR DRAIN IS | | | LOCATED THAT IS SHOWN ON E-2 ISOMETRIC. | | | | | | REVIEW BY LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | (561) 805-6692 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | | | | |
|