Plan Review Notes
Plan Review Notes For Permit 11010398
Permit Number 11010398
Review Stop P
Sequence Number 1
Notes
Date Text
2011-01-27 11:11:25FBC PLUMBING 2007 PLAN REVIEW #1
 DENIED:
  
 1. IF STALLS ARE PROVIDED IN THE TOILET ROOMS, THEN
 THEY SHALL COMPLY WITH 11-4.17 FIGURE(E)
  
 2. FBC PLUNBING 403.1 MINIMUM NUMBER OF FIXTURES. 1
 DRINKING FOUNTAIN PER 1,000 OCCUPANTS IS REQUIRED.
  
 3. FBC 106.3.5.1.3 WATER PIPING DIAGRAM IS REQUIRED.
  
 3. PLEASE INDICATE ON PLAN WHERE THE FLOOR DRAIN IS
 LOCATED THAT IS SHOWN ON E-2 ISOMETRIC.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR