| 2011-02-02 09:26:12 | **DENIED** |
| | |
| | 1. PAGE M-1 SHOWS AHU LOCATED IN STORAGE/SPRINKLER |
| | EQUIPMENT ROOM. THIS ROOM ALSO APPEARS TO SERVE AS A |
| | RETURN AIR PLENUM. RETURN AIR PLENUMS SHALL BE LIMITED |
| | TO UNINHABITED CRAWL SPACES, AREAS ABOVE A CEILING OR |
| | BELOW THE FLOOR, ATTIC SPACES AND MECHANICAL EQUIPMENT |
| | ROOMS PER FBC-M 602.1. |
| | |
| | 2. PAGE M-1 SHOWS A PVC CONDENSATE LINE IN THE SAME |
| | RETURN AIR PLENUM. COMBUSTIBLE MATERIALS (SUCH AS PVC) |
| | ARE NOT PERMITTED IN PLENUMS PER FBC-M 602.2.1. |
| | |
| | 3. PAGE A-1 SHOWS AN AHU-2 IN THE SAME ROOM AS AHU-1, |
| | BUT THIS AHU DOES NOT APPEAR ON PAGE M-1. PLEASE |
| | CLARIFY AND COORDINATE DRAWINGS. CONSTRUCTION DOCUMENTS |
| | SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| | OF THIS CODE PER FBC-B 106.1.1. |
| | |
| | 4. PAGE M-1 SHOWS 10X8 O/A DUCT PENETRATING A FIRE |
| | RATED CHASE. THIS PENETRATION OF A SHAFT ENCLOSURE |
| | SHALL BE PROTECTED WITH LISTED FIRE AND SMOKE DAMPERS |
| | INSTALLED IN ACCORDANCE WITH THEIR LISTING PER FBC-M |
| | 607.5.5. |
| | |
| | 5. PAGE M-1 SHOWS CONDENSATE LINE DISCHARGING IN THE |
| | ALLEY. CONDENSATE FROM THE AHU SHALL BE CONVEYED FROM |
| | THE DRAIN PAN OUTLET TO AN APPROVED PLACE OF DISPOSAL. |
| | CONDENSATE SHALL NOT DISCHARGE INTO A STREET, ALLEY OR |
| | OTHER AREAS SO AS TO CAUSE A NUISANCE PER FBC-M |
| | 307.2.1. |
| | |
| | 6. PLAN SHOWS NEW CONDENSER STAND ON ROOF. |
| | PRE-ENGINEERED A/C STAND REQUIRE PRODUCT APPROVAL PER |
| | FAC RULE 9N-3. PROVIDE PRODUCT APPROVAL, APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD FOR THIS PROJECT, PER |
| | FBC-M 106.3.3. |
| | |
| | NOTE: TEST AND BALANCE REPORT REQUIRED FOR FINAL |
| | INSPECTION PER FBC-M 403.3.4. |
| | |
| | NOTE: PLAN SHOWS WHAT APPEARS TO BE EXPOSED DUCT BOARD |
| | THROUGHOUT THE SPACE. PLEASE NOTE THAT EXPOSED |
| | DUCTBOARD CAN NOT BE PAINTED AS IT VOIDS THE SLAME |
| | SPREAD/SMOKE DEVELOPMENT RATING ASSOCIATED WITH THE |
| | UL181 LISTING OF THE DUCT. |
| | |
| | |