| 2011-01-27 14:32:23 | 306 CLEMATIS STREET |
| | PERMIT #11010398 |
| | 1ST REVIEW - FIRE |
| | |
| | |
| | ALL INSIDE STAIRS SERVING AS AN EXIT OR EXIT COMPONENT |
| | SHALL BE ENCLOSED (REFERENCE: SECTION 7.2.2.5.1.1 OF |
| | FLORIDA FIRE PREVENTION CODE - NFPA 101). |
| | |
| | AN EXIT ENCLOSURE SHALL PROVIDE A CONTINUOUS PROTECTED |
| | PATH OF TRAVEL TO AN EXIT DISCHARGE (REFERENCE: SECTION |
| | 7.1.3.2.2 OF FLORIDA FIRE PREVENTION CODE - NFPA 101). |
| | |
| | PROVIDE STAIR RAILINGS IN ACCORDANCE WITH THE |
| | REQUIREMENTS OF CHAPTER 7 OF NFPA 101 - LIFE SAFETY |
| | CODE. |
| | |
| | IN BUILDINGS PROTECTED THROUGHOUT BY A SPRINKLER |
| | SYSTEM, THE MINIMUM SEPARATION DISTANCE BETWEEN TWO |
| | EXITS OR EXIT ACCESS DOORS SHALL BE NOT LESS THAN |
| | ONE-THIRD THE LENGTH OF THE MAXIMUM OVERALL DIAGONAL |
| | DIMENSION OF THE BUILDING OR AREA BEING SERVED |
| | (REFERENCE: SECTION 7.5.1.3.3 OF FLORIDA FIRE |
| | PREVENTION CODE - NFPA 101). |
| | |
| | LIMITED INFORMATION HAS BEEN PROVIDED FOR THE SECOND |
| | AND THIRD FLOOR. DESCRIBE HOW THESE FLOORS WILL BE |
| | USED. NO PORTABLE FIRE EXTINGUISHERS OR EXIT SIGNS HAVE |
| | BEEN PROVIDED. NO OCCUPANT LOAD HAS BEEN ESTABLISHED |
| | FOR THESE FLOORS. |
| | |
| | FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION |
| | 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES |
| | SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE |
| | DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC FIRE |
| | SPRINKLERS. |
| | |
| | THREE FIRE ALARM HORN/STROBE DEVICES ARE SHOWN ON THE |
| | FIRST FLOOR ONLY. DESCRIBE WHAT TYPE OF FIRE ALARM |
| | SYSTEM IS INTENDED FOR THIS SPACE. |
| | |
| | PROVIDE TACTILE SIGNAGE AT EXITS. |
| | |
| | DESCRIBE THE QUANTITY OF WINE AND ALCOHOL THAT WILL BE |
| | LOCATED ON THE PREMISES. |
| | |
| | SHEET LS-1 MENTIONS A NEW KITCHEN. EXPLAIN. |
| | |
| | EVERY FLOOR SERVED BY THE ELEVATOR SHALL HAVE AN |
| | ELEVATOR LOBBY. BARRIERS FORMING THE ELEVATOR LOBBY |
| | SHALL HAVE A FIRE RESISTANCE RATING OF NOT LESS THAN 1 |
| | HOUR (REFERENCE: SECTION 7.2.13.3 OF FLORIDA FIRE |
| | PREVENTION CODE - NFPA 101). |
| | |
| | ELEVATOR'S SHALL BE PROVIDED WITH FIREFIGHTER'S |
| | EMERGENCY OPERATIONS. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |