Notes
Date Text
2011-01-28 15:38:29PROVIDE AUTOMATIC LIGHTING CONTROL AND LIGHTING
 DENSITIES. FBC 13-415 ABC.1.2
 A GFCI PROTECTED RECEPTACLE IS REQUIRED ON THE ROOF FOR
 SERVICING THE AIR-CONDITIONING EQUIPMENT. NEC 210.63
 BATHROOM RECEPTACLES TO BE GFCI PROTECTED. NEC 210.8
 PROVIDE THE FAULT CURRENT CALCULATION AND INTERRUPTING
 RATING FOR THE NEW SERVICE EQUIPMENT. NEC 110.9
 SEPARATE THE STORAGE AREA FROM THE ELECTRICAL SERVICE
 EQUIPMENT. NEC 110.26
 PROVIDE CLARIFICATION AS TO THE LOCATION AND REQUIRED
 ACCESS TO THE MAIN ELECTRIC DISCONNECT. NEC 230.33,
 230.70
  