| 2011-01-28 15:38:29 | PROVIDE AUTOMATIC LIGHTING CONTROL AND LIGHTING | | | DENSITIES. FBC 13-415 ABC.1.2 | | | A GFCI PROTECTED RECEPTACLE IS REQUIRED ON THE ROOF FOR | | | SERVICING THE AIR-CONDITIONING EQUIPMENT. NEC 210.63 | | | BATHROOM RECEPTACLES TO BE GFCI PROTECTED. NEC 210.8 | | | PROVIDE THE FAULT CURRENT CALCULATION AND INTERRUPTING | | | RATING FOR THE NEW SERVICE EQUIPMENT. NEC 110.9 | | | SEPARATE THE STORAGE AREA FROM THE ELECTRICAL SERVICE | | | EQUIPMENT. NEC 110.26 | | | PROVIDE CLARIFICATION AS TO THE LOCATION AND REQUIRED | | | ACCESS TO THE MAIN ELECTRIC DISCONNECT. NEC 230.33, | | | 230.70 | | | |
|