| Plan Review Notes For Permit 11010372 |
| Permit Number |
11010372 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-03-01 09:06:20 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR | | | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS | | | FS471. SEE SHEET E1, NOT SIGNED AND SEALED. IT IS | | | RECOMMENDED THAT EITHER THE ENGINEER COME TO OUR | | | DEPARTMENT TO SIGN AND SEAL THE DOCUMENT OR THE | | | CONTRACTOR REQUEST ONE REVIEWED AND CSD STAMPED SET AT | | | THE FRONT COUNTER OF CONSTRUCTION SERVICES TO TAKE TO | | | THE ENGINEER TO SIGN AND SEAL. | | | | | | ALTERNATIVELY, THE CONTRACTOR CAN RESUBMIT A NEW SHEET | | | E1 BUT THIS WILL REQUIRE NEW ZONING AND ELECTRIC | | | REVIEWS. | | | | | | 2. THE LIGHT POLE ENGINEERING DOES NOT STATE WIND | | | EXPOSURE CLASSIFICATION. THERE IS A STATEMENT THAT THIS | | | INCLUDES HVHZ; THEREFORE, MY ASSUMPTION IS THAT THE | | | CALCULATIONS ARE FOR EXPOSURE C. PLEASE ADVISE IF THIS | | | IS NOT CORRECT. IN THE FUTURE, PLEASE INCLUDE EXPOSURE | | | CLASSIFICATION ON THE PLAN. | | | | | | | | | |
|