| Plan Review Notes For Permit 11010358 |
| Permit Number |
11010358 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-02-01 16:24:13 | PLANS DENIED | | | 1) PLEASE PROVIDE THE MANUAL (D) WITH THE PLANS. | | | 2) REFER TO SECTION 601.4 BALANCED RETURN AIR 2007 FBC | | | (M) . | | | 3) VAV # 3-1 EQUIPMENT SCHEDULE SHOWS THE MAX. CFM. 830 | | | . PLANS SHOW 850 CFM. | | | 4) PLEASE PROVIDE ON THE PLANS A DETAIL ON THE CURB TIE | | | DOWN TO ROOF AND THE RTU TIE DOWN TO CURB IF THEY ARE | | | NOT EXISTING. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|