2011-02-01 16:24:13PLANS DENIED
 1) PLEASE PROVIDE THE MANUAL (D) WITH THE PLANS.
 2) REFER TO SECTION 601.4 BALANCED RETURN AIR 2007 FBC
 (M) .
 3) VAV # 3-1 EQUIPMENT SCHEDULE SHOWS THE MAX. CFM. 830
 . PLANS SHOW 850 CFM.
 4) PLEASE PROVIDE ON THE PLANS A DETAIL ON THE CURB TIE
 DOWN TO ROOF AND THE RTU TIE DOWN TO CURB IF THEY ARE
 NOT EXISTING.