| Plan Review Notes For Permit 11010358 |
| Permit Number |
11010358 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-02-03 17:55:08 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. PROVIDE MORE INFORMATION REGARDING THE ROOF DRAIN | | | REPAIRS AND RELOCATION. FBC 15. | | | | | | 2. SPECIFY INSULATION R VALUE, SEE SCOPE. | | | | | | 3. M002 REFERS TO "NEW HARDPAN CEILINGS," PROVIDE A | | | DETAIL AND LOCATION OF INSTALLATION (PHASE 2 & 3 PLAN). | | | DETAIL IS INCLUDED IN ALTERNATE 1, CLARIFY IF THIS IS | | | TO BE USED THROUGHOUT AND CLARIFY LOCATIONS OF DRYWALL | | | INSTALLATION. | | | | | | | | | 4. M002 REFERS TO NOAS, PROVIDE TWO SETS. | | | | | | 5. OBTAIN AN ASBESTOS REMOVAL PERMIT FROM HEALTH | | | DEPARTMENT. | | | | | | 6. A BUILDING PERMIT IS REQUIRED FOR DRYWALL | | | INSTALLATION. PLEASE SUBMIT APPLICATION OR BE ADVISED | | | THAT A SUB PERMIT WILL BE REQUIRED PRIOR TO | | | COMMENCEMENT. | | | | | | |
|