Plan Review Notes
Plan Review Notes For Permit 11010337
Permit Number 11010337
Review Stop P
Sequence Number 1
Notes
Date Text
2011-02-02 10:04:36FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 1. PLUMBING 403.1 MINIMUN REQUIRED FIXTURES- BUSINESS:
 1 DRINKING FOUNTAIN IS REQUIRED PER 100 OCCUPANTS.
  
 2. PLUMBING 909.1 THE SINK IN ROOM 111 IS RUNNING
 THROUGH THE WET VENT FOR THE RESTROOMS. ONLY THE
 FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO
 THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL
 WET VENT.
  
 3. 106.3.5.1.3 PLUMBING (3) DRAWING REQUIRED FOR WATER
 PIPING.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR