| Notes |
| Date |
Text |
| 2011-02-02 10:04:36 | FBC PLUMBING 2007 REVIEW #1 | | | DENIED: | | | | | | 1. PLUMBING 403.1 MINIMUN REQUIRED FIXTURES- BUSINESS: | | | 1 DRINKING FOUNTAIN IS REQUIRED PER 100 OCCUPANTS. | | | | | | 2. PLUMBING 909.1 THE SINK IN ROOM 111 IS RUNNING | | | THROUGH THE WET VENT FOR THE RESTROOMS. ONLY THE | | | FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO | | | THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL | | | FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL | | | WET VENT. | | | | | | 3. 106.3.5.1.3 PLUMBING (3) DRAWING REQUIRED FOR WATER | | | PIPING. | | | | | | REVIEW BY LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | (561) 805-6692 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|