Plan Review Notes
Plan Review Notes For Permit 11010337
Permit Number 11010337
Review Stop M
Sequence Number 1
Notes
Date Text
2011-02-14 11:40:48PLANS DENIED
 1) EQUIPMENT SCHEDULE SHOWS ONE A/C UNIT PLAN SHOWS
 TWO.
 2) PROVIDE FRESH AIR CALCULATIONS ON THE PLANS.
 3) REFER TO SECTION 606.3.1 SUPPLY AIR AND SECTION
 606.3 INSTALLATION FBC (M) 2007 .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732