Plan Review Notes
Plan Review Notes For Permit 11010337
Permit Number 11010337
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-01-27 11:30:101001 NORTH DIXIE HIGHWAY
 PERMIT #11010337
 REVIEW COMMENTS - FIRE
  
 DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION
 CODE 2007 EDITION (NFPA 1 AND NFPA 101 - 2006 EDITION
 WITH FLORIDA AMENDMENTS).
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS WITH A MINIMUM
 RATING OF 2A:10BC ALONG THE PATH OF EGRESS.
 EXTINGUISHERS SHALL HAVE A CURRENT SERVICE TAG PROVIDED
 BY A LICENSED FIRE EXTINGUISHER COMPANY.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE AT LEAST SIX-INCHES IN HEIGHT AND
 SHALL CONTRAST THE BACKGROUND (REFERENCE: SECTION
 10.12.1.2 OF THE FLORIDA FIRE PREVENTION CODE - NFPA
 1).
  
 PROVIDE DOOR LOCK AND LATCH RELEASING MECHANISM
 INFORMATION.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW