| Notes |
| Date |
Text |
| 2011-01-27 11:30:10 | 1001 NORTH DIXIE HIGHWAY | | | PERMIT #11010337 | | | REVIEW COMMENTS - FIRE | | | | | | DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION | | | CODE 2007 EDITION (NFPA 1 AND NFPA 101 - 2006 EDITION | | | WITH FLORIDA AMENDMENTS). | | | | | | ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS | | | OF NFPA 241. | | | | | | PROVIDE PORTABLE FIRE EXTINGUISHERS WITH A MINIMUM | | | RATING OF 2A:10BC ALONG THE PATH OF EGRESS. | | | EXTINGUISHERS SHALL HAVE A CURRENT SERVICE TAG PROVIDED | | | BY A LICENSED FIRE EXTINGUISHER COMPANY. | | | | | | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY | | | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING | | | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM | | | WWW.KNOXBOX.COM. | | | | | | PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET. | | | NUMBERS SHALL BE AT LEAST SIX-INCHES IN HEIGHT AND | | | SHALL CONTRAST THE BACKGROUND (REFERENCE: SECTION | | | 10.12.1.2 OF THE FLORIDA FIRE PREVENTION CODE - NFPA | | | 1). | | | | | | PROVIDE DOOR LOCK AND LATCH RELEASING MECHANISM | | | INFORMATION. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW |
|