Plan Review Notes
Plan Review Notes For Permit 11010337
Permit Number 11010337
Review Stop E
Sequence Number 1
Notes
Date Text
2011-01-19 15:37:24PROVIDE A BONDING BAR AT THE SERVICE. NEC 250.94
 PROVIDE AUTOMATIC LIGHTING CONTROL AND LIGHTING
 DENSITIES. FBC 13-415 ABC.1.2
 PROVIDE ELECTRIC FAULT CURRENT CALCULATION FOR SERVICE
 EQUIPMENT AND PANELBOARD. NEC 110.9, 110.10
 PROVIDE GFCI PROTECTED RECEPTACLE ON ROOF FOR SERVICING
 THE AIR-CONDITIONING EQUIPMENT. NEC 210.63
 PROVIDE A 1200 VA, 20 AMP, SIGN CIRCUIT. NEC 660.5,
 220.14(F)
 PROVIDE EMERGENCY LIGHTING. FBC 1006
 INCLUDE ALL LOADS AT 100% IN THE SERVICE CALCULATION.
 NEC 220 PART III
 ELECTRIC SERVICE REQUIRES 3/0 CONDUCTORS FOR 200 AMP.
 NEC T. 310.16
 INDICATE THE SIZE OF THE SERVICE FEEDERS AND LOCATION
 OF THE FEEDER. NEC. 310.8
 INDICATE THE MAIN DISCONNECT IS SUITABLE FOR A WET
 LOCATION. NEC 330.6
  
 NOTE:
 A SEPARATE PERMIT WITH A PLAN IS REQUIRED FOR VOICE AND
 DATA.
  
 ROBERT LECKY, ELECTRIC PLANS EXAMINER, 561-805-6718
  
  