| Plan Review Notes For Permit 11010333 |
| Permit Number |
11010333 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-01-21 12:07:42 | APPROVED WITH PROVISO ON PLANS. | | | | | | PROVIDE A BONDING BAR AT THE SERVICE. NEC 250.94 | | | AT LEAST ONE WALL SWITCHED-CONTROLLED LIGHTING OUTLET | | | SHALL BE INSTALLED IN EVERY HABITABLE ROOM. NEC 210.70 | | | RECEPTACLES SHALL BE SPACED SO THAT AT NO POINT ALONG | | | THE FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A | | | RECEPTACLE OUTLET. NEC 210.52 (A)(2). | | | ADDITIONAL RECEPTACLES ARE REQUIRED FOR ANY WALL SPACE | | | MORE THAN 2 FEET IN WIDTH. NEC 210.52 (A) (2). | | | BEDROOM RECEPTACLES MUST BE PROTECTED WITH AFCI'S. NEC | | | 210.12 | | | THE SMOKE DETECTORS MUST BE INTERCONNECTED. FBC R313.2 | | | GFCI PROTECTION IS REQUIRED FOR RECEPTACLES IN | | | KITCHENS. NEC 210.8 | | | | | | ROBERT LECKY, ELECTRIC PLANS EXAMINER, 561-805-6718 | | | |
|