| 2011-03-02 11:36:24 | RESIDENTIAL (R3) ALTERATION BUILDING REVIEW SECOND |
| | CHECKLIST. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- SCOPE OF WORK SHOWN ON THE PERMIT APPLICATION |
| | DOESN'T MATCH SCOPE OF WORK SHOWN ON PLANS SUBMITTED. |
| | PROPOSED FLOOR PLAN SHOWS NEW LAYOUT FOR THE MASTER |
| | BEDROOM, NEW KITCHEN, NEW FRAMED OPENINGS, NEW A/C, NEW |
| | ELECTRICAL ON WHOLE BUILDING, ETC. REVISE SCOPE OF WORK |
| | AND VALUATION ON PERMIT APPLICATION AS REQUIRED BY SEC. |
| | 108.3 CITY AMENDMENTS TO FBC. (REPEAT COMMENT. NOT |
| | ADDRESSED AT ALL). |
| | |
| | 2- PROVIDE PRODUCT APPROVAL ( 2 COPIES) AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) SINGLE HUNG WINDOWS. NEW NOA 09-0316.10 SUBMITTED |
| | WAS SUPERSEDED BY MIAMI-DADE WEBSITE. NEED TO PROVIDE |
| | CURRENT NOA. |
| | |
| | B) HURRICANE SHUTTERS: MISSING THE INSTALLATION |
| | SCHEDULE. AND, CLEARLY MARK ON SHUTTERS DRAWINGS ANCHOR |
| | TYPE AND SPACING TO BE USED TO VERIFY COMPLIANCE WITH |
| | THE CALCULATED DESIGN PRESSURES. |
| | |
| | C) SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS AND |
| | SECTIONS. PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE |
| | AND PAGE SHOWING THE CONNECTOR. THIS APPLIES TO |
| | STRUCTURAL CONNECTORS ONLY. (REPEAT COMMENT. NOT |
| | ADDRESSED AT ALL). |
| | |
| | 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| | DOOR PRODUCT APPROVAL FL8838-R1 NEEDS TO BE REVIEWED BY |
| | THE ENGINEER. |
| | AND, ENGINEER TO CLARIFY WHY APPROVING NOA 06-0406.11. |
| | THIS PRODUCT APPROVAL IS ONLY FOR THE DOOR SKIN. THIS |
| | IS A COMPONENT APPROVAL ONLY NOT THE DOOR PRODUCT |
| | APPROVAL. |
| | |
| | 4- PROVIDE SITE PLAN PLAN OR SURVEY TO SHOW DISTANCE |
| | FROM MASTER BEDROOM SIDE TO THE ADJACENT GARAGE. TO |
| | PROVIDE/VERIFY COMPLIANCE WITH THE SEPARATION |
| | REQUIREMENTS OF SEC. R309.2 AND EXTERIOR WALLS AND |
| | OPENINGS PROTECTION REQUIREMENTS OF TABLE R302.1. |
| | SITE PLAN ON SHEET A-2 DOESN'T MATCH AERIAL VIEW SHOWN |
| | ON PAPA RECORDS. IT'S MISSING THE ADJACENT GARAGE THAT |
| | IS PARALLEL TO THE MASTER BEDROOM. |
| | |
| | 5- SHEET A-1: |
| | A) WIND DESIGN INFORMATION WAS REVISED TO EXPOSURE "B". |
| | STILL DESIGN PRESSURES SHOWN DON'T CORRESPOND TO |
| | EXPOSURE "B" OR EXPOSURE "C" ACCORDING TO THE SIZE OF |
| | WINDOW AND LOCATION ON THE WALL. PROVIDE ACTUAL |
| | CALCULATIONS FOR THE DESIGN PRESSURES AND REVISE AS |
| | REQUIRED. SEC. 106.1.2 OF CITY AMENDMENTS TO FBC TO |
| | VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. |
| | R301 OF 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | B) REVISE THE DESIGN PRESSURES FOR THE EXTERIOR DOORS. |
| | DESIGN PRESSURES SHOWN ON EXTERIOR ELEVATIONS DON'T |
| | CORRESPOND TO THE DESIGN PRESSURES ACCORDING TO THE |
| | DOOR SIZE. PROVIDE ACTUAL CALCULATIONS. SEC. 106.1.2 |
| | CITY AMENDMENTS TO FBC. |
| | |
| | C) UPDATE BUILDING NOTES TO REFLECT ACTUAL BUILDING |
| | CONDITIONS. INFORMATION DOESN'T MATCH FLOOR PLAN. |
| | (REPEAT COMMENT). |
| | |
| | 6- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK |
| | STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. |
| | (REPEAT COMMENT. NOT ADDRESSED AT ALL). |
| | |
| | 7- REVISED SHEET A-1: |
| | A) NEW WOOD INFILL DETAIL: SPECIFY HOW ARE THE 2X4'S |
| | STUDS ATTACHED AT THE ENDS. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC. SPECIFY WALL SHEATHING AND EXTERIOR |
| | WALL FINISH. |
| | |
| | B) SCOPE OF WORK DOESN'T MATCH FLOOR PLANS. THERE ARE |
| | NEW WALLS SHOWN ON FLOOR PLAN. ALSO, THE WALL LEGEND |
| | DOESN'T MATCH FLOOR PLAN. REVISE AS REQUIRED. |
| | |
| | C) LOCATION MAP IS MISSING THE INFORMATION. NO PICTURE |
| | SHOWN NOW. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |