2011-01-19 17:10:53REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. INCLUDE OCCUPANT LOAD IN THE FRESH AIR CALCULATION,
 SHEET M1, FBC M403.3.
  
 2. SHOW HOW BALANCED RETURN AIR WILL BE PROVIDED, FBC
 M601.4.
  
 3. SEPARATE PLANS, PERMITS, AND REVIEWS REQUIRED FOR
 THE HOOD, WALK IN COOLER, AND WALK IN FREEZER. PLEASE
 REMOVE APPLICABLE DETAILS.
  