2011-01-28 14:57:00FBC FUEL GAS REVIEW #1
 DENIED:
  
 1. KITCHEN EQUIPMENT PLAN DOES NOT MATCH WITH THE
 APPLIANCES SHOWN ON P-1 GAS DRAWING.
  
 2. WATER HEATER IS LISTED AS GAS ON A-1, AND AS
 ELECTRIC ON E-2, AND MISSING ON P-1 GAS RISER.
  
 3. PLEASE LABEL AUTOMATIC GAS SHUTOFF AND SHOW THAT IT
 IS BELOW CEILING WITH A VALVE AND UNION UPSTREAM.
  
  