| Plan Review Notes For Permit 11010182 |
| Permit Number |
11010182 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-01-28 14:57:00 | FBC FUEL GAS REVIEW #1 | | | DENIED: | | | | | | 1. KITCHEN EQUIPMENT PLAN DOES NOT MATCH WITH THE | | | APPLIANCES SHOWN ON P-1 GAS DRAWING. | | | | | | 2. WATER HEATER IS LISTED AS GAS ON A-1, AND AS | | | ELECTRIC ON E-2, AND MISSING ON P-1 GAS RISER. | | | | | | 3. PLEASE LABEL AUTOMATIC GAS SHUTOFF AND SHOW THAT IT | | | IS BELOW CEILING WITH A VALVE AND UNION UPSTREAM. | | | | | | | | | REVIEW BY LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | (561) 805-6692 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|