2011-01-20 14:10:401558 PALM BEACH LAKES BOULEVARD, SUITE #5
 PERMIT #11010182
 REVIEW COMMENTS - FIRE
  
 *****DRAWINGS REQUIRE FIRE DEPARTMENT STAMP ONCE
 BUILDING DEPT COMMENTS HAVE BEEN ADDRESSED*****
  
  
 PROVIDE THE OCCUPANCY TYPE OF THE PREVIOUS TENANT
 OCCUPYING THIS SUITE.
  
 RESTAURANTS WITH AN OCCUPANT LOAD LESS THAN 50 PERSONS
 ARE CLASSIFIED AS MERCANTILE OCCUPANCIES.
  
 PROVIDE K-TYPE PORTABLE FIRE EXTINGUISHER IN KITCHEN
 AREA. PROVIDE ABC-TYPE PORTABLE FIRE EXTINGUISHER IN
 NON-KITCHEN AREAS.
  
 PROVIDE MINIMUM 8-INCH STEEL/GLASS BAFFLE BETWEEN THE
 FRYERS AND SURFACE FLAMES OF THE WOK.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION/MODIFACTION OF THE FIRE SPRINKLER SYSTEM,
 FIRE ALARM SYSTEM AND KITCHEN HOOD SUPPRESSION SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW