| Plan Review Notes For Permit 11010182 |
| Permit Number |
11010182 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-01-14 15:10:40 | THE FOLLOWING WAS NOTED ON THE SINGLE SET OF PLANS | | | SUBMITTED. | | | 3/0 CONDUCTORS ARE REQUIRED FOR A 200 AMP ELECTRIC | | | SERVICE. NEC 310.16 | | | ROBERT LECKY, ELECTRIC PLANS EXAMINER, 561-805-6718 |
|