| 2011-01-19 19:16:20 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. COVER LETTER STATES THAT THE SCOPE IS ENTIRELY NON |
| | STRUCTURAL, BUT THERE ARE NUMEROUS DETAILS FOR ROOF |
| | OPENINGS AND RTU DETAILS. PLEASE REMOVE OR REVISE |
| | LETTER TO CORRELATE WITH THE WORK PROPOSED. |
| | |
| | 2. COVER LETTER, COVER SHEET, AND VARIOUS DETAILS REFER |
| | TO EXPOSURE CLASSIFICATION AS B, AND WIND SPEEDS OF |
| | 120, 140, AN 146. THE CITY OF WEST PALM BEACH IS |
| | ENTIRELY IN THE 140MPH WIND ZONE, THIS PARCEL IS |
| | LOCATED IN EXPOSURE C BASED ON AERIALS. PLEASE REVISE |
| | AFFECTED DETAILS AND NOTES. FBC1609. |
| | |
| | 3. THERE ARE NUMEROUS RTU DETAILS. PLEASE LABEL EACH |
| | DETAIL WHICH IS APPLICABLE TO THIS JOB AND INCLUDE A |
| | DETAIL MARKER ON THE FLOOR PLAN, OR OTHERWISE IDENTIFY |
| | INSTALLATION LOCATION AND PURPOSE OF THE VARIOUS |
| | DETAILS. REMOVE DETAILS WHICH ARE NOT APPLICABLE TO |
| | THIS JOB. |
| | |
| | 4. COMPONENT & CLADDING PRESSURES ARE FOR 120 EXPOSURE |
| | B AND ARE TOO LOW FOR THIS PROJECT. EITHER REMOVE THE |
| | NON COMPLIANT PRESSURES OR REVISE TO COMPLY. C & C |
| | DESIGN PRESSURES DO NOT APPEAR TO BE APPLICABLE TO THIS |
| | JOB. |
| | |
| | 5. "PROJECT DATA" ON COVER SHEET STATE THAT THIS IS A |
| | LEVEL 2 ALTERATION. THIS PROJECT ALSO APPEARS TO BE A |
| | CHANGE OF OCCUPANCY; BASED ON OUR RECORDS, THIS WAS A |
| | BUSINESS OCCUPANCY. PLEASE SEE FBC EXISTING BUILDING |
| | CHAPTER 9 (OR APPLICABLE SECTION BAED ON METHOD OF |
| | COMPLIANCE). SHOW COMPLIANCE WITH ALL REQUIREMENTS FOR |
| | A CHANGE OF OCCUPANCY. PLEASE ALSO SEE FBC 309, |
| | MERCANTILE OCCUPANCIES SHALL INCLUDE "RESTAURANTS AND |
| | DRINKING ESTABLISHMENTS WITH AN OCCUPANT LOAD OF LESS |
| | THAN 50 PERSONS." |
| | |
| | 6. PLEASE PROVIDE MORE INFORMATION TO SHOW COMPLIANCE |
| | WITH FBC TABLE 1004.1.1. DESIGNER HAS USED 15 SF PER |
| | PERSON; THIS IS FOR SEATING WITH TABLES AND CHAIRS. |
| | WILL NON FIXED SEATING BE PROVIDED? WAITING AREA SHOULD |
| | USE 5 SF PER OCCUPANT. OFFICE AREA WAS NOT INCLUDED IN |
| | CALCULATION. PLEASE CONTACT ME IF YOU WISH TO DISCUSS. |
| | |
| | 7. COVER SHEET STATES THAT THIS IS A TYPE IIB BUILDING, |
| | BUT OUR RECORDS SHOW WOOD TRUSSES ON THE PITCHED |
| | SECTIONS OF THE ROOF, SEE FBC 602.2. PLEASE EITHER |
| | REVISE OR EXPLAIN TYPE IIB. |
| | |
| | 8. FBC 11-7.2(1), COUNTER AT CASH REGISTER, SHOW |
| | LENGTH. |
| | |
| | 9. FBC 11-4.32, PROVIDE A DETAIL FOR THE FIXED SEATING. |
| | |
| | 10. FBC 11-5.5, PROVIDE A DETAIL FOR THE "SERVING |
| | AREA." |
| | |
| | 11. FBC 11-5.5, 11-5.3, SHOW WIDTH OF FOOD SERVICE LINE |
| | AND ALSO SHOW ACCESS AISLE TO FIXED SEATING. |
| | |
| | 12. FBC 11-5.6, WILL SELF SERVICE SHELVES OR DISPENSERS |
| | BE PROVIDED? PROVIDE A DETAIL IF REQUIRED. |
| | |
| | 13. FBC 11-4.1(3), WORK AREAS ARE TO BE DESIGNED SO |
| | THAT EMPLOYEES CAN APPROACH, ENTER, AND EXIT. SEE THE |
| | "OFFICE," DOOR LACKS MANEUVERING CLEARANCE, SEE FBC 11 |
| | FIGURE 25. |
| | |
| | 14. DBPR APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE, |
| | FS509. PLEASE SEE HTTP://WWW.MYFLORIDALICENSE.COM/DBPR/ |
| | HR/FORMS/PLANREVIEWFORMS.HTML FOR MORE INFORMATION. |
| | |
| | |