Plan Review Notes
Plan Review Notes For Permit 11010182
Permit Number 11010182
Review Stop B
Sequence Number 1
Notes
Date Text
2011-01-19 19:16:20****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. COVER LETTER STATES THAT THE SCOPE IS ENTIRELY NON
 STRUCTURAL, BUT THERE ARE NUMEROUS DETAILS FOR ROOF
 OPENINGS AND RTU DETAILS. PLEASE REMOVE OR REVISE
 LETTER TO CORRELATE WITH THE WORK PROPOSED.
  
 2. COVER LETTER, COVER SHEET, AND VARIOUS DETAILS REFER
 TO EXPOSURE CLASSIFICATION AS B, AND WIND SPEEDS OF
 120, 140, AN 146. THE CITY OF WEST PALM BEACH IS
 ENTIRELY IN THE 140MPH WIND ZONE, THIS PARCEL IS
 LOCATED IN EXPOSURE C BASED ON AERIALS. PLEASE REVISE
 AFFECTED DETAILS AND NOTES. FBC1609.
  
 3. THERE ARE NUMEROUS RTU DETAILS. PLEASE LABEL EACH
 DETAIL WHICH IS APPLICABLE TO THIS JOB AND INCLUDE A
 DETAIL MARKER ON THE FLOOR PLAN, OR OTHERWISE IDENTIFY
 INSTALLATION LOCATION AND PURPOSE OF THE VARIOUS
 DETAILS. REMOVE DETAILS WHICH ARE NOT APPLICABLE TO
 THIS JOB.
  
 4. COMPONENT & CLADDING PRESSURES ARE FOR 120 EXPOSURE
 B AND ARE TOO LOW FOR THIS PROJECT. EITHER REMOVE THE
 NON COMPLIANT PRESSURES OR REVISE TO COMPLY. C & C
 DESIGN PRESSURES DO NOT APPEAR TO BE APPLICABLE TO THIS
 JOB.
  
 5. "PROJECT DATA" ON COVER SHEET STATE THAT THIS IS A
 LEVEL 2 ALTERATION. THIS PROJECT ALSO APPEARS TO BE A
 CHANGE OF OCCUPANCY; BASED ON OUR RECORDS, THIS WAS A
 BUSINESS OCCUPANCY. PLEASE SEE FBC EXISTING BUILDING
 CHAPTER 9 (OR APPLICABLE SECTION BAED ON METHOD OF
 COMPLIANCE). SHOW COMPLIANCE WITH ALL REQUIREMENTS FOR
 A CHANGE OF OCCUPANCY. PLEASE ALSO SEE FBC 309,
 MERCANTILE OCCUPANCIES SHALL INCLUDE "RESTAURANTS AND
 DRINKING ESTABLISHMENTS WITH AN OCCUPANT LOAD OF LESS
 THAN 50 PERSONS."
  
 6. PLEASE PROVIDE MORE INFORMATION TO SHOW COMPLIANCE
 WITH FBC TABLE 1004.1.1. DESIGNER HAS USED 15 SF PER
 PERSON; THIS IS FOR SEATING WITH TABLES AND CHAIRS.
 WILL NON FIXED SEATING BE PROVIDED? WAITING AREA SHOULD
 USE 5 SF PER OCCUPANT. OFFICE AREA WAS NOT INCLUDED IN
 CALCULATION. PLEASE CONTACT ME IF YOU WISH TO DISCUSS.
  
 7. COVER SHEET STATES THAT THIS IS A TYPE IIB BUILDING,
 BUT OUR RECORDS SHOW WOOD TRUSSES ON THE PITCHED
 SECTIONS OF THE ROOF, SEE FBC 602.2. PLEASE EITHER
 REVISE OR EXPLAIN TYPE IIB.
  
 8. FBC 11-7.2(1), COUNTER AT CASH REGISTER, SHOW
 LENGTH.
  
 9. FBC 11-4.32, PROVIDE A DETAIL FOR THE FIXED SEATING.
  
 10. FBC 11-5.5, PROVIDE A DETAIL FOR THE "SERVING
 AREA."
  
 11. FBC 11-5.5, 11-5.3, SHOW WIDTH OF FOOD SERVICE LINE
 AND ALSO SHOW ACCESS AISLE TO FIXED SEATING.
  
 12. FBC 11-5.6, WILL SELF SERVICE SHELVES OR DISPENSERS
 BE PROVIDED? PROVIDE A DETAIL IF REQUIRED.
  
 13. FBC 11-4.1(3), WORK AREAS ARE TO BE DESIGNED SO
 THAT EMPLOYEES CAN APPROACH, ENTER, AND EXIT. SEE THE
 "OFFICE," DOOR LACKS MANEUVERING CLEARANCE, SEE FBC 11
 FIGURE 25.
  
 14. DBPR APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE,
 FS509. PLEASE SEE HTTP://WWW.MYFLORIDALICENSE.COM/DBPR/
 HR/FORMS/PLANREVIEWFORMS.HTML FOR MORE INFORMATION.
  
  