| 2011-01-14 12:16:09 | MECHANICAL PROVISO | | | | | | FBCR M1602.4 REQUIRES THE RETURN TRANSFER DUCTS TO BE | | | ONE AND ONE HALF THE CROSS SECTIONAL AREA OF THE SUPPLY | | | DUCT ENTERING THE ROOM OR SPACE. THE SUPPLY TO THE | | | MASTER BEDROOM INCLUDES THE BATHROOM. | | | | | | |
|