2011-02-23 10:14:39PLEASE ADDRESS THE PREVIOUS ELECTRICAL COMMENTS.
 REPLACING SCREENING WITH WINDOWS CHANGES THE USE OF THE
 ROOM AS DEFINED BY THE ELECTRICAL AND BUILDING CODE.
 THE NEW ROOM IS CONSIDERED HABITABLE SPACE AND REQUIRES
 RECEPTACLES AND LIGHTING IN ACCORDANCE WITH THE
 ELECTRIC CODE. NEC 210.52 (A), 210.70, 210.8.
  