| Plan Review Notes For Permit 11010154 |
| Permit Number |
11010154 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-02-10 10:38:40 | ****PROVISO**** | | | NFPA 99C 2005 5.1.37.1.2 (2) WAGD SHOWN IS CONNECTED TO | | | MED VAC LINE ADDRESS THE FOLLOWING AT FIRST INSPECTION: | | | FLAMMABLE ANESTHETICS OR OTHER FLAMMABLE VAPORS SHALL | | | BE DILUTED BELOW THE LOWER FLAMMABLE LIMIT PRIOR TO THE | | | MEDICAL-SURGICAL VACUUM SYSTEM OR THE VACUUM PUMPS | | | SHALL COMPLY WITH 5.1.3.7.2.1(2) | | | | | | | | | ***NOTE**** | | | 1. SEE PROJECT MANUAL PAGE 22 6313 ??? 7 A (3) GAS | | | MANIFOLDS SHALL HAVE SHUTOFF VALVE, PRESSURE | | | REGULATOR, CHECK VALVE, AND PRESSURE GAGE. | | | | | | 2. MED GAS PERMIT REQUIRED BEFORE ANY MED GAS DEMO. | | | | | | REVIEW BY LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | (561) 805-6692 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | | | | |
|