Plan Review Notes For Permit 11010154
Permit Number 11010154
Review Stop P
Sequence Number 1
Notes
Date Text
2011-02-10 10:38:40****PROVISO****
 NFPA 99C 2005 5.1.37.1.2 (2) WAGD SHOWN IS CONNECTED TO
 MED VAC LINE ADDRESS THE FOLLOWING AT FIRST INSPECTION:
 FLAMMABLE ANESTHETICS OR OTHER FLAMMABLE VAPORS SHALL
 BE DILUTED BELOW THE LOWER FLAMMABLE LIMIT PRIOR TO THE
 MEDICAL-SURGICAL VACUUM SYSTEM OR THE VACUUM PUMPS
 SHALL COMPLY WITH 5.1.3.7.2.1(2)
  
  
 ***NOTE****
 1. SEE PROJECT MANUAL PAGE 22 6313 ??? 7 A (3) GAS
 MANIFOLDS SHALL HAVE SHUTOFF VALVE, PRESSURE
 REGULATOR, CHECK VALVE, AND PRESSURE GAGE.
  
 2. MED GAS PERMIT REQUIRED BEFORE ANY MED GAS DEMO.
  
 REVIEW BY LARRY WAGNER