| 2011-05-31 09:33:20 | ****CORRECTIONS**** |
| | |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | COMMENTS FROM PREVIOUS LIST, NOT ADDRESSED. |
| | |
| | 1. ADDRESSED. |
| | |
| | 2. PROVIDE CALCULATIONS FOR THE ALUMINUM I BEAMS TO |
| | SHOW RESISTANCE TO WIND, DEAD AND LIVE LOADS FBC R301. |
| | |
| | 3. SEE PREVIOUS LIST, ON THE FLOOR PLAN PROVIDE ROOM |
| | DESIGNATION FOR THE ADJACENT ROOMS WHICH OPEN INTO THE |
| | EXISTING PORCH (BY EITHER WINDOW OR DOOR). IF BEDROOMS |
| | ARE AFFECTED, SHOW ALTERNATE COMPLIANCE WITH EMERGENCY |
| | MEANS OF ESCAPE REQUIREMENTS, FBC R310. |
| | |
| | 4. IT APPEARS THAT A PORTION OF TH PORCH WALL IS A |
| | TENANT SEPARATION WALL. A FIRE RATED WALL IS REQUIRED. |
| | SHOW TENANT SEPARATIONS ON THE PLAN, FBC R317 AND |
| | PROVIDE A DETAIL FOR THE NEW TENANT SEPARATION WALL |
| | WHICH IS NOW REQUIRED (NEW STORAGE ROOM AND EXISTING |
| | TENANT SEPARATION). |
| | |
| | 5. SHOW TRAVEL TO EXIT, FBC CHAPTER 3. IT IS NOT CLEAR |
| | THROUGH WHAT ADJACENT ROOMS AN OCCUPANT IS REQUIRED TO |
| | TRAVEL THROUGH IN ORDER TO REACH AN EXIT. |
| | |
| | 6. ADDRESSED. |
| | |
| | 7. COMMENT FROM PREVIOUS LISTS - THIS PARCEL IS LOCATED |
| | IN A HIGH HAZARD FLOOD ZONE, A9. THE MINIMUM FLOOR |
| | ELEVATION REQUIRED IS 13'6". OUR RECORDS SHOW THAT THE |
| | EXISTING STRUCTURE HAS AN ELEVATION OF APPROXIMATELY |
| | 12', BUT A 6" STEP DOWN IS PROPSED. SEE NFIP |
| | REQUIREMENTS FOR ADDITIONS, PROPOSED NEW HABITABLE |
| | SPACE IS TO BE A MINIMUM OF 6" ABOVE BASE FLOOD |
| | ELEVATION PER CITY OF WEST PALM BEACH MUNICIPAL CODE |
| | 94-546(B). |
| | |
| | REVIEW 3 - PLAN HAS BEEN REVISED TO SHOW A STORAGE AREA |
| | RATHER THAN HABITABLE SPACE. FLOOD VENTS ARE NOW SHOWN. |
| | PLEASE PROVIDE ELEVATION CERTIFICATE (SEE COMMENT #23) |
| | WHICH SHOULD SHOW COMPLIANCE FOR FLOOD VENTS. SEE THE |
| | FEMA/NFIP WEBSITE FOR MORE INFORMATION. |
| | |
| | HTTP://WWW.FEMA.GOV/LIBRARY/FILE?TYPE=PUBLISHEDFILE&FIL |
| | E=FEMA_TB_1__1_.PDF&FILEID=CB212200-A517-11DD-B825-0011 |
| | 85636A87 |
| | |
| | 8. PROVIDE A COPY OF A SURVEY WHICH SHOWS DISTANCE OF |
| | PROPOSED NEW ROOM TO PROPERTY LINES. |
| | |
| | 9. ADDRESSED. |
| | |
| | 10. THIS PARCEL HAS AN EXPIRED PERMIT 03121693, PLEASE |
| | ADDRESS. |
| | |
| | 11-13. ADDRESSED. |
| | |
| | 14. PROVIDE MORE INFORMATION REGARDING THE EXISTING |
| | ROOF PANELS. PORCHES CAN BE DESIGNED WITH AN IMPORTANCE |
| | FACTOR OF .77, NOT CLEAR IF THE EXISTING ROOF STRUCTURE |
| | CAN MEET REQUIREMENT FOR HABITABLE SPACE WITH AN |
| | IMPORTANCE FACTOR OF 1.0. |
| | |
| | 15. PROVIDE OVER HEAD DOOR PRODUCT APPROVAL. |
| | |
| | 16. BOND BREAK REQUIRED, FBC R 703.6.3. |
| | |
| | 17. SPECIFY SILL PLATE (SIZE AND MATERIAL). PT |
| | REQUIRED. |
| | |
| | 18. FRAMING DETAIL CONFLICTS WITH OTHER DETAILS; |
| | FRAMING DETAIL SHOWS A WOOD FRAME WALL BUT OTHER |
| | DETAILS SHOW A CONCRETE BLOCK KNEE WALL. FBC 106. |
| | |
| | 19. HOW HAS IT BEEN DETERMINED THAT THERE ARE EXISTING |
| | FILLED CELLS ON EACH SIDE OF EACH PROPOSED NEW DOOR AND |
| | WINDOW INSTALLATION? EITHER PROVIDE INFORMATION |
| | REGARDING HOW THIS HAS BEEN DETERMINED OR PROVIDE A |
| | DETAIL FOR THE NEW FILLED CELLS. |
| | |
| | 3RD REVIEW, PLEASE PROVIDE PLANS AND PERMIT NUMBER FOR |
| | THE EXISTING PORCH. EXISTING CONDITIONS NOT CLEAR. |
| | |
| | 20. ADDRESSED. |
| | |
| | 21. PROVIDE A COST BREAKDOWN FOR THIS PROJECT. |
| | |
| | 22. IT IS NOT CLEAR HOW THE ROOF IS SUPPORTED BY A KNEE |
| | WALL, NO COLUMNS SHOWN. PROVIDE MORE INFORMATION. |
| | |
| | 3RD REVIEW, SEE COMMENT #19. |
| | |
| | 23. PROVIDE A PROPERLY COMPLETED ELEVATION CERTIFICATE |
| | (CONSTRUCTION DRAWINGS). HTTP://WWW.FEMA.GOV/PLAN/PREVE |
| | NT/FLOODPLAIN/NFIPKEYWORDS/ELEVATION_CERTIFICATE.SHTM |
| | |