Plan Review Notes
Plan Review Notes For Permit 11010148
Permit Number 11010148
Review Stop B
Sequence Number 2
Notes
Date Text
2011-04-28 10:17:59****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. WHEN RESUBMITTING, PROVIDE TWO SIGNED, SEALED, DATED
 SETS OF PLANS FS471.
  
 2. PROVIDE CALCULATIONS FOR THE ALUMINUM I BEAMS TO
 SHOW RESISTANCE TO WIND, DEAD AND LIVE LOADS FBC R301.
  
 3. SEE PREVIOUS LIST, ON THE FLOOR PLAN PROVIDE ROOM
 DESIGNATION FOR THE ADJACENT ROOMS WHICH OPEN INTO THE
 EXISTING PORCH (BY EITHER WINDOW OR DOOR). IF BEDROOMS
 ARE AFFECTED, SHOW ALTERNATE COMPLIANCE WITH EMERGENCY
 MEANS OF ESCAPE REQUIREMENTS, FBC R310.
  
 4. IT APPEARS THAT A PORTION OF TH PORCH WALL IS A
 TENANT SEPARATION WALL. A FIRE RATED WALL IS REQUIRED.
 SHOW TENANT SEPARATIONS ON THE PLAN, FBC R317 AND
 PROVIDE A DETAIL FOR THE NEW TENANT SEPARATION WALL
 WHICH IS NOW REQUIRED (NEW STORAGE ROOM AND EXISTING
 TENANT SEPARATION).
  
 5. SHOW TRAVEL TO EXIT, FBC CHAPTER 3. IT IS NOT CLEAR
 THROUGH WHAT ADJACENT ROOMS AN OCCUPANT IS REQUIRED TO
 TRAVEL THROUGH IN ORDER TO REACH AN EXIT.
  
 6. EXPLAIN, "WIND INFO" A1 SHOWS A SINGLE FAMILY HOME,
 TWO APARTMENT ARE SHOWN ON THE AREA CALCS.
  
 7. THIS PARCEL IS LOCATED IN A HIGH HAZARD FLOOD ZONE,
 A9. THE MINIMUM FLOOR ELEVATION REQUIRED IS 13'6". OUR
 RECORDS SHOW THAT THE EXISTING STRUCTURE HAS AN
 ELEVATION OF APPROXIMATELY 12', BUT A 6" STEP DOWN IS
 PROPSED. SEE NFIP REQUIREMENTS FOR ADDITIONS, PROPOSED
 NEW HABITABLE SPACE IS TO BE A MINIMUM OF 6" ABOVE BASE
 FLOOD ELEVATION PER CITY OF WEST PALM BEACH MUNICIPAL
 CODE 94-546(B).
  
 8. PROVIDE A COPY OF A SURVEY WHICH SHOWS DISTANCE OF
 PROPOSED NEW ROOM TO PROPERTY LINES.
  
 9. IMPACT FEES MAY BE DUE TO PALM BEACH COUNTY,
 561-233-5025 FOR MORE INFORMATION.
  
 10. THIS PARCEL HAS AN EXPIRED PERMIT 03121693, PLEASE
 ADDRESS.
  
 11. R305.1, HABITABLE ROOMS TO HAVE A CEILING HEIGHT
 NOT LESS THAN 7', SEE ALSO EXCEPTIONS. SHOW CEILING
 HEIGHT AFTER SLAB IS ELEVATED TO 13'6".
  
 12. ENERGY CALCS REQUIRED, FBC R 1100.
  
 13. SHOW INSULATION IN CEILING, FBC R 1100.
  
 14. PROVIDE MORE INFORMATION REGARDING THE EXISTING
 ROOF PANELS. PORCHES CAN BE DESIGNED WITH AN IMPORTANCE
 FACTOR OF .77, NOT CLEAR IF THE EXISTING ROOF STRUCTURE
 CAN MEET REQUIREMENT FOR HABITABLE SPACE WITH AN
 IMPORTANCE FACTOR OF 1.0.
  
 15. PROVIDE OVER HEAD DOOR PRODUCT APPROVAL.
  
 16. BOND BREAK REQUIRED, FBC R 703.6.3.
  
 17. SPECIFY SILL PLATE (SIZE AND MATERIAL). PT
 REQUIRED.
  
 18. FRAMING DETAIL CONFLICTS WITH OTHER DETAILS;
 FRAMING DETAIL SHOWS A WOOD FRAME WALL BUT OTHER
 DETAILS SHOW A CONCRETE BLOCK KNEE WALL. FBC 106.
  
 19. HOW HAS IT BEEN DETERMINED THAT THERE ARE EXISTING
 FILLED CELLS ON EACH SIDE OF EACH PROPOSED NEW DOOR AND
 WINDOW INSTALLATION? EITHER PROVIDE INFORMATION
 REGARDING HOW THIS HAS BEEN DETERMINED OR PROVIDE A
 DETAIL FOR THE NEW FILLED CELLS.
  
 20. THERE IS A REFERENCE TO TRUSS ENGINEERING ON THE
 PLAN, PLEASE PROVIDE.
  
 21. PROVIDE A COST BREAKDOWN FOR THIS PROJECT.
  
 22. IT IS NOT CLEAR HOW THE ROOF IS SUPPORTED BY A KNEE
 WALL, NO COLUMNS SHOWN. PROVIDE MORE INFORMATION.
  
 23. PROVIDE A PROPERLY COMPLETED ELEVATION CERTIFICATE
 (CONSTRUCTION DRAWINGS). HTTP://WWW.FEMA.GOV/PLAN/PREVE
 NT/FLOODPLAIN/NFIPKEYWORDS/ELEVATION_CERTIFICATE.SHTM
  
  
  
  
  
  