| Notes |
| Date |
Text |
| 2011-01-12 09:36:03 | PLEASE REVISE THE PLANS TO ACCURATELY REFLECT THE | | | FOLLOWING: | | | | | | A GFCI PROTECTED OUTLET IS REQUIRED AT THE REAR | | | ELEVATION. NEC 210.8, 210.52 (E) (1) | | | NOTE ON THE PLAN THE REQUIREMENT FOR TAMPER RESISTANT | | | RECEPTACLES. NEC 406.11 | | | | | | THE PLAN SHOWS FOUR LIGHT SWITCHES BUT DOES NOT | | | INDICATE WHAT THEY CONTROL. | | | | | | AT LEAST ONE WALL SWITCHED-CONTROLLED LIGHTING OUTLET | | | SHALL BE INSTALLED. NEC 210.70 (A)(1). | | | AT LEAST ONE SWITCH CONTROLLED LIGHTING OUTLET SHALL BE | | | PROVIDED ON THE EXTERIOR SIDE OF THE REAR ENTRANCE. NEC | | | 210.70 (A) (2) (B). | | | | | | | | | ROBERT LECKY, ELECTRICAL PLANS REVIEW, 561-805-6718 |
|