| Plan Review Notes For Permit 11010146 |
| Permit Number |
11010146 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-01-18 13:32:16 | 205 DATURA STREET | | | PERMIT #11010146 | | | REVIEW COMMENTS - FIRE | | | | | | REPEAT COMMENT: SYSTEM DESIGNER SHALL BE INDENTIFIED ON | | | THE PLANS PER NFPA 72 REQUIREMENTS. | | | | | | REPEAT COMMENT: NO AUDIBLE NOTIFICATION APPLIANCES ARE | | | SHOWN IN THE 2ND, 3RD AND 4TH FLOOR NORTH AREAS. | | | | | | REPEAT COMMENT: INDICATE LOCATIONS OF DUCT SMOKE | | | DETECTORS AND REMOTE TEST STATIONS. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|