Plan Review Notes
Plan Review Notes For Permit 11010133
Permit Number 11010133
Review Stop B
Sequence Number 2
Notes
Date Text
2011-01-11 17:09:42RE-ROOF BUILDING REVIEW SECOND CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- MEMBRANE ATTACHMENT: ENGINEER SPECIFIES 4"O.C.
 FASTENER SPACING AT PERIMETER AND CORNER AREAS.
 CALCULATIONS ON SECOND PAGE SUBMITTED SHOWS FASTENER
 SPACING AT 3.6" AND 2.7" RESPECTIVELY. CALCULATIONS AND
 MEMBRANE ATTACHMENT SPECIFICATION DON'T MATCH. ON THE
 OTHER HAND ENGINEER TO SEE SEC. 4.2 OF RAS 137 FOR
 MINIMUM FASTENER SEPARATION REQUIRED. REVISE AS
 REQUIRED.
  
 2- INSULATION ATTACHMENT: ENGINEER SPECIFIES 6
 FASTENERS AT PERIMETER AND 8 FASTENERS AT CORNER AREAS.
 ACCORDING TO SEC. 9.1.2 OF RAS 117 ALL FRACTIONS SHALL
 BE ROUNDED UP TO THE NEXT WHOLE NUMBER. NOT ROUNDED
 DOWN. ALSO, REVISE EXPOSURE SHOWN ON SHEET 3. THIS
 BUILDING IS IN EXPOSURE "C" NOT "B". AND CLARIFY WHERE
 IS THE -45PSF MAXIMUM DESIGN PRESSURE FOR THE
 INSULATION ATTACHMENT TAKEN FROM?. REVISE AS REQUIRED.
  
  
 3- FASTENERS WITHDRAWAL RESISTANCE TEST (TAS 105) WILL
 BE REQUIRED FOR MECHANICALLY FASTENED ROOF COVERINGS.
 SEC. 4.3 OF RAS 137.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712