| Plan Review Notes For Permit 11010118 |
| Permit Number |
11010118 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-01-12 14:04:41 | 1 HARVARD CIRCLE, SUITE #102 | | | PERMIT #11010118 | | | REVIEW COMMENTS - FIRE | | | | | | FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION | | | 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES | | | SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE | | | DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC FIRE | | | SPRINKLERS. NOTE: SEPARATE PLANS AND PERMITS ARE | | | REQUIRED FOR THE INSTALLATION OF THE FIRE SPRINKLER | | | SYSTEM AND FIRE ALARM SYSTEM. | | | | | | THE PLANS SHOW DOORS WITH EXISTING CARD-READER ACCESS. | | | INDICATE HOW EGRESS IS ACHIEVED. | | | | | | COORDINATE REFLECTED CEILING PLAN AND ELECTRICAL | | | DRAWING EXIT SIGN LOCATIONS. | | | | | | FLUSH BOLTS ARE NOT PERMITTED AT THE TOP AND BOTTOM OF | | | THE DOOR LEAF UNLESS THE RELEASING MECHANISM COMPLIES | | | WITH SECTION 7.2.1.5.9.1 OF THE FLORIDA FIRE PREVENTION | | | CODE 2007 EDITION (NFPA 101). | | | | | | PROVIDE TACTILE SIGNAGE AT EXIT DOOR LOCATIONS. | | | | | | PER LOCAL CODE AMENDMENTS, DUCT SMOKE DETECTORS SHALL | | | INITIATE A GENERAL FIRE ALARM CONDITION. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|