2011-04-29 10:25:432007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE RAS 117 CALCULATIONS ARE INCORRECT. THE ROOF
 PITCH FOR THE COVERED PATIO IS 0 TO 7 DEGREES. WHICH
 MAKES THE PRESSURES FOR EXPOSURE C - 42.7 PSF FOR ROOF
 ZONE 1, -71.6 PSF FOR ROOF ZONE 2 AND - 107.7 PSF FOR
 ROOF ZONE THREE. ROOFING APPLICATION STANDARD (RAS) NO.
 117 SECTION 8.1 REQUIRES THAT THE MINIMUM FASTENER
 SEPARATION SHALL NOT BE LESS THAN 4 IN. ON CENTER.
 PLEASE SUBMIT CORRECTED RAS 117 CALCULATIONS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714