| Plan Review Notes For Permit 11010095 |
| Permit Number |
11010095 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2011-04-29 10:25:43 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) THE RAS 117 CALCULATIONS ARE INCORRECT. THE ROOF | | | PITCH FOR THE COVERED PATIO IS 0 TO 7 DEGREES. WHICH | | | MAKES THE PRESSURES FOR EXPOSURE C - 42.7 PSF FOR ROOF | | | ZONE 1, -71.6 PSF FOR ROOF ZONE 2 AND - 107.7 PSF FOR | | | ROOF ZONE THREE. ROOFING APPLICATION STANDARD (RAS) NO. | | | 117 SECTION 8.1 REQUIRES THAT THE MINIMUM FASTENER | | | SEPARATION SHALL NOT BE LESS THAN 4 IN. ON CENTER. | | | PLEASE SUBMIT CORRECTED RAS 117 CALCULATIONS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|