2011-04-04 13:34:042007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE RAS 117 CALCULATIONS THAT WERE SUBMITTED FOR THE
 GAF MODIFIED ROOF COVERING SYSTEM ARE BASED ON EXPOSURE
 CATEGORY B AND THE PROJECT IS LOCATED IN EXPOSURE C.
 THE PLANS THAT WERE SUBMITTED ALSO SPECIFY EXPOSURE C.
 PLEASE SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117
 CALCS. FOR 140 MPH EXPOSURE C.
  
 2) THE DESIGN WIND UPLIFT PRESSURES PRESSURES LISTED IN
 THE RAS 117 CALCULATIONS ARE LOW. PER ASCE 7-05 FIGURE
 6-3 ON PAGE 43, WITH AN EFFECTIVE WIND AREA OF 10
 SQUARE FEET OR LESS THE UPLIFT PRESSURES FOR A ROOF
 SLOPE OF 0 TO 7 DEGREES AND MRH 30 FT LOCATED IN 140
 MPH EXPOSURE B ARE -35.3 PSF FOR ROOF ZONE 1, -59.2 PSF
 FOR ROOF ZONE 2 AND -89.0 PSF FOR ROOF ZONE 3. THESE
 PRESSURES WILL NEED TO BE MULTIPLIED BY THE APPROPRIATE
 ADJUSTMENT FACTOR FROM THE TABLE ON PAGE 44 FOR
 EXPOSURE C AND MEAN ROOF HEIGHT OF THE STRUCTURE.
  
 3) FBC R806 ROOF VENTILATION, REQUIRES THE ENCLOSED
 SPACES BETWEEN RAFTERS TO HAVE CROSS VENTILATION FOR
 EACH SEPARATE SPACE BY VENTILATION OPENINGS. SHOW
 COMPLIANCE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW